Field Device Termination; Terminating The Wiring; Other Connections; Repeater Connection - Zeta NPAD 2 Installation Manual

Analogue addressable fire alarm control panel
Table of Contents

Advertisement

PREMIER AD INSTALLATION MANUAL.

10. FIELD DEVICE TERMINATION

10.1 TERMINATING THE WIRING.

LO OP 1A
SND 1
LO OP 1B
-
+
-
+
-
CO NN19 CO NN12 CO NN20 CO NN13 CO NN21 CO NN14 CO NN22 CO NN18 CO NN15 CO NN16 CO NN17 CO NN28
CO NN27
MAKE SURE ANY SPARE
ENTRY HOLES ARE
COVERED WITH THE
GROMMETS PROVIDED
CO NN27
Figure 6: Detector and Sounder Circuit Connection

11 OTHER CONNECTIONS

11.1 REPEATER CONNECTION

The Premier AD has an RS485 connection for a serial repeater. The repeaters are display only (no
control). A single repeater can be powered from the panel`s Auxiliary Supply. If 2 or more are to be
connected, then they must be powered from external 24V power supplies. The panel supports up to 4
repeaters.
Connections
Premier AD (Termination PCB)
SERIAL REPEATER +
SERIAL REPEATER -
AUX SUP +
AUX SUP -

11.2 SERIAL PRINTER CONNECTION

The Premier AD has a connection for a serial printer. The printer will print out panel events as they
occur. The recommended printer is an Epson LQ300 II+. The serial port on the Premier AD is
configured to this printer`s default settings.
Connections
Premier AD
25 pin D connector
TX
Pin 3 (RX)
RX
Pin 2 (TX)
GND
Pin 7 (GND)
CTS
Pin 4 (RTS)
DSR
Pin 20 (DTR)
Approved Document No: GLT.MAN-105A
Issue : 2.02
Authorised: GH
Brass Glands
SND 2
LO OP 2A
SND 3
LO OP 2B
SND 4
FIRE RELAY
FAULT RELAY
CLASS CH
SERIAL RE P AETER
AUX SUP
+
-
+
-
+
-
+
-
+
-
+
NO CM NC
NO CM NC
-
+
-
+
-
+
-
+
CO NN24 CO NN25 CO NN23
CO NN4
CO NN30 CO NN2
+
-
AC AC
BATTERY
Date: 16/07/2007
INLET MAINS
SUPPLY
All cables entering the enclosure
should have brass cable glands,
which will ensure a good ground to
the steel EMC cable grounding plate.
The Detector and Sounder circuits
should
CO NN6
appropriate connector block on the
Termination PCB as shown in Figure
6 below.
CO NN29
LIVE NEUT- EAR TH
RAL
All screens should be terminated at
the brass earthing strip as shown in
Figure 6
(For detailed detector and alarm
circuit wiring diagrams, please refer
to pages 4 and 5.)
AD Repeater
COM-
COM +
+28V
0V
Serial Port Settings
Setting
Baud Rate
Data Bits
Stop bits
Parity
Flow Control
Software:PANEL:R1107 & LOOP:R1062
be
connected
Value
19200
8
1
NO
Hardware
PAGE 17