9. AUXILIARY INPUTS & OUTPUTS

9.1 AUXILIARY INPUT WIRING EXAMPLES

There is one non-latching auxiliary input connection on the Fire Alarm Panel.
Class Change Input (CC): This will energise all alarm outputs continuously when the CC terminals
are shorted together. (This includes the 4 conventional sounder outputs & any loop powered
sounders.)
Typical auxiliary input wiring options
CLASS
CHANGE
The termination for the above inputs must be as indicated on the main PCB (See page 15). The
Earthing of the cable screens should be as shown on page 9.
9.2 AUXILIARY OUTPUT WIRING (VOLTAGE FREE CHANGEOVER
CONTACTS)
Auxiliary Fire Output (AUX): Changes over in any fire condition, and be used for driving local fire
fighting equipment such as sprinkler systems, magnetic door holders, air conditioning shut off, etc.
Fault Output (FAULT): This Output is energised in the quiescent condition. In a fault condition, the
output relay turns off, to ensure failsafe operation even in the event of total power loss. That is, the
normally open contact will be closed when there is no fault, and open when there is a fault. This
should be taken into account when any device is connected to the fault relay.
Typical auxiliary output wiring
Trigger I/P
NOTE: THE NC CONTACT
IS OPEN WHEN THERE IS
NO FAULT.
NO CM NC
FAULT RELAY
Trigger I/P
NO CM NC
FIRE RELAY
The termination for the above inputs must be as indicated on the main PCB (See page 31). The
Earthing of the cable screens should be as shown on page 17.
Approved Document No: GLT.MAN-105A
Issue : 2.02
Authorised: GH
CLASS
CHANGE
FAULT
INDICATION
DEVICE
AUTO-
DIALER
Date: 16/07/2007
Tends to be more expensive
Maximum 32 per loop for quick start/stop
Quiescent current high
Uses device address.
4-8 second start & stop time.
Always configured as common sounders
Needs detector present to operate.
Does not operate during sounder test mode
Needs Extra Cabling.
Needs External PSU
Maximum 32 per loop for quick start/stop
Quiescent current high
Uses device address.
AUX FIRE RELAY
CM NO
2nd Fire Alarm
The fault relay is used to
connect to a remote
indication device
The fire relay can be used to connect
to various devices which are activated
on a fire alarm. Eg. Auto dialer ,
magnetic door release (24V), sprinkler
system etc.
Software:PANEL:R1107 & LOOP:R1062
PAGE 16