13. DISABLEMENT

On the Premier AD, there are 2 disablement options. A whole zone of detectors can
be disabled, or an individual point can be disabled. Both types of disablement can
be used at the same time if required.

13.1 ZONE DISABLEMENT

To aid commissioning and assist routine maintenance checks, any of the zones or the sounder
circuits can be disabled.
When a zone (or sounder cct) is disabled, the panel will not respond to any fault or fire signals it
receives from DETECTORS from that zone. Call points will remain operational.
This might be used if the system requires routine maintenance, and the customer needs the system
to continue running, but doesn't want spurious false alarms.
The panel will respond in the usual manner to any events in any non-disabled zones.
The premier AD allows the 4 conventional sounder circuits to be disabled individually, and
also allows the loop powered sounders to be disabled

13.2 TO PROGRAMME ZONE (OR SOUNDERS) AS DISABLED

Any number of zones (or the sounders) can be disabled, but it is good practice to only disable one
zone at a time.
1.
Insert and turn control key to enabled position;
2.
Press DISABLE button and the screen will show:
ZONE DISABLEMENT ZONE 1. The panel is now in
SELECT DISABLEMENT MODE.
3.
Press DISABLEMENT SELECT until the required zone or
sounder circuit is DISPLAYED. Press DISABLEMENT
CONFIRM button. The screen will now show that the zone is
disabled, and the Zone or Sounder LED will
come on steady, along with the GENERAL DISABLEMENT LED.
This section is now disabled. (NOTE: Call points in this zone
will still be active. To disable the call points as well, disable them individually as points
– see 13.3)
4.
If more than one zone (or sounder) needs to be disabled, then press DISABLEMENT SELECT
again until the required zone (or sounder) is selected.
5.
If the panel needs to be taken out of SELECT DISABLEMENT MODE (eg to silence a fault on
another part of the system), Either press DISABLEMENT button, or turn the keyswitch off, then
back on again.
6.
Once all the maintenance work has been done the zones need to be enabled again. If the
panel is still in SELECT DISABLEMENT MODE, jump to paragraph 7, otherwise, turn the
keyswitch to controls enabled, press DISABLE button. The panel is now in SELECT
DISABLEMENT MODE
7.
Press the DISABLEMENT SELECT button until the disabled zone is displayed on the screen.
Press DISABLEMENT CONFIRM button to de-select disablement. Scroll to any other disabled
zone and enable in the same way. When all zones are enabled again, the GENERAL
DISABLEMENT LED will turn off. Turn the keyswitch to off position to return the system to
normal. (NOTE: This will also enable any points individually disabled in that zone)

13.3 POINT DISABLEMENT

The Premier AL panel can also disable individual devices (detector,
call point, sounder or interface). To do this, enter CONFIGURATION
MENU 2 and select EDIT DEVICE. Select the required device, them
press DISABLE button. The Device label now flashed between the
programmed label and Device Disabled. The general disablement LED
will also be lit. This device is now disabled. To re-enable the device,
Approved Document No: GLT.MAN-105A
Issue : 2.02
Authorised: GH
Date: 16/07/2007
Software:PANEL:R1107 & LOOP:R1062
Zone Disablement
Zone
1
Enabled
Single Devices:
Zone Disablement
Zone
3
Disabled
Single Devices:
Optical
Analog:
25
Normal
Device Disabled
Zone:01
Lp:1 Ad:016
0
0
PAGE 23