Zeta INFINITY ID2/4 Installation Manual

Zeta INFINITY ID2/4 Installation Manual

Intelligent 2 wire fire detection system with 'id' technology
Hide thumbs Also See for INFINITY ID2/4:
Table of Contents

Advertisement

Quick Links

INFINITY ID2 INSTALLATION MANUAL.
INTELLIGENT 2 WIRE FIRE DETECTION SYSTEM
INSTALLATION MANUAL
Approved Document No: GLT-211-7-1
Issue 1.9 Author: MG/NJ
www.acornfiresecurity.com
WITH 'ID' TECHNOLOGY
Date: 06/04/2016
www.acornfiresecurity.com
Software Versions: PANEL 1.N & LOOP O.N

Advertisement

Table of Contents
loading

Summary of Contents for Zeta INFINITY ID2/4

  • Page 1 www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N INTELLIGENT 2 WIRE FIRE DETECTION SYSTEM WITH ‘ID’ TECHNOLOGY INSTALLATION MANUAL Approved Document No: GLT-211-7-1 Issue 1.9 Author: MG/NJ Date: 06/04/2016 www.acornfiresecurity.com...
  • Page 2: Table Of Contents

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N CONTENTS 1. SAFETY INFORMATION ............................3 1.1 Installation Information ..........................3 1.2 Safety Precautions during Normal Operation of Panel ................3 1.3 Battery Information ............................ 3 1.4 Product Disposal at the end of its working life ................... 3 2.
  • Page 3 www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 12.8.1 DEFAULT SETTING ........................... 25 12.8.2 SETTING INDIVIDUAL I/O UNIT OPERATION - RELAY ................26 12.8.3 SETTING INDIVIDUAL I/O UNIT OPERATION - INPUT ..............26 12.8.4 I/O UNIT OPERATION - PANEL LINK ....................26 12.8.5 CONFIGURING ALARM OUTPUT RESOUND OPERATION ..............
  • Page 4: Safety Information

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 1. SAFETY INFORMATION WARNING: Read this section completely before commencing installation. 1.1 Installation Information THIS FIRE ALARM CONTROL PANEL IS CLASS 1 EQUIPMENT AND MUST BE EARTHED This equipment must be installed and maintained by a qualified and technically experienced person. This C.I.E.must be wired to a fused spur rated at 3A.
  • Page 5: Product Design Information

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 2. PRODUCT DESIGN INFORMATION 2.1 Fire Alarm Control Section EN 54-2:1997 +A1 - Fire The ID2 Fire Alarm Control and Indicating Equipment (CIE) has been designed to Detection & Fire Alarm Systems – Control & Indicating Equipment As well as meeting the requirements of EN 54-2:1997 +A1, the Infinity ID2 also has the following options with requirements:- Clause 7.8...
  • Page 6: Panel Description & Design Concept

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 3.0 Panel description & design concept The ID2 is an eight zone intelligent fire alarm control panel designed to EN54 part 2 & 4. The ID2 has been designed to use zone powered sounders but also has 2 conventional sounder circuits. All sounders on a ID2 panel will activate on any alarm.
  • Page 7: Using This Manual

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 4 USING THIS MANUAL It is beyond the scope of this manual to teach the user all the intricacies of fire alarm system design. If in doubt about what is required, read BS 5839: Pt 1: 2013 “Fire Detection and Alarm Systems for buildings (UK Code of Practice for System Design, Installation, commissioning and maintenance)”...
  • Page 8: Designing A System

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 5 DESIGNING A SYSTEM This manual is not designed to teach Fire Alarm System design. It is assumed that the System has been designed by a competent person, and that the installer has an understanding of Fire Alarm System components and their use.
  • Page 9: Installing The System

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 6. INSTALLING THE SYSTEM 6.1 Considerations before Installation 6.1.1 MOUNTING THE CONTROL PANEL The control panel should be installed in accordance with the following recommendations:- The panel should be close to the main entrance of the building, so that it can be viewed by any fire- •...
  • Page 10: First Fix

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 6.2 First Fix 6.2.1 MOUNTING THE FIRE ALARM PANEL The ID2 comes with many cable entry holes. If another entry hole is required, it is strongly recommended that the, the termination PCBs should be removed and stored in a safe place.
  • Page 11: Connecting The Mains Power

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 6.2.4 CONNECTING THE MAINS POWER Figure 3: Power Supply PCB layout and Mains connection details The panel should be connected to 220-240V AC by a 3A rated spur to the fuse box with 1mm to 2.5mm 3-core cable.
  • Page 12: Connecting The Batteries

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 6.2.5 CONNECTING THE BATTERIES Figure 4: Battery location and connection details Although there are many sizes of suitable battery, the sizes we usually recommend for the ID2 are 12V 7Ah, To calculate the exact requirement, use the equation in section 20.1, STANDBY BATTERY CALCULATIONS The two batteries are wired in series to give 24 Volts.
  • Page 13: Zone Wiring

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 7. ZONE WIRING The ID2 can be wired with up to 8 separate radial circuits each with 15 devices per circuit. It may also be wired as a single loop. When Wired as a Loop, Zone 1 is used as Loop OUT (Side A), and Zone 2 is used as Loop IN (Side B) Each termination is identified on the terminal labels.
  • Page 14: Specific Device Wiring Instructions

    7.1 Specific device wiring instructions All products will come with their own wiring instructions. This should be used when connecting a product. But as a general guideline, here are the connection details of most Zeta Addressable products. 7.1.1 CP3/AD Manual Call Point The CP3/AD call point has a built in isolator which can be wired in circuit or not used.
  • Page 15: Zai - Mi Input Module

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N Deep Base MKII-CB/D Common Base MKII-CB 7.1.3 ZAI - MI Input Module The end of line resistor value is 20K and the trigger resistor value is 1 K . 7.1.4 ZAIO –...
  • Page 16: Zasc - Mi Sounder Control Module

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 7.1.5 ZASC – MI Sounder Control Module The ZASC requires an external 24vdc power supply (as shown in the above diagram). The EOL for the sounder circuit is 10KΩ. When using the ZASC make sure the PSU being used has a fault output relay, so that in the event of a power supply fault it is reported to the control panel.
  • Page 17: Xtratone Sounder/Sounder Flasher

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 7.1.7 Xtratone Sounder/Sounder Flasher The Xtratone sounder or sounder flasher is a wall mount sounder. The programming of the sounder is done via the D.I.L switch mounted on the inside (front). It may also be programmed via the handheld programming tool. Connecting the sounder is done using the terminals in the back box of the device.
  • Page 18: Addressable Remote Led Indicator

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 7.1.9 Addressable Remote LED Indicator Ceiling Mount (MKII-ARL/C) Wall Mount (MKII-ARL/W) There are two versions of the remote LED, Wall mounted and Ceiling mounted. The ceiling mounted version requires a standard detector base.
  • Page 19: Setting The Device Zone & Id (Detectors, Call Points & Sounders)

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 7.2 Setting the device zone & ID (detectors, call points & sounders) The ID2 divides the loop addresses into zones and Ids. The panel translates the address into a zone and ID. Each zone starts with ID1, in order to simplify the addressing.
  • Page 20 www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N ZONE ZONE Approved Document No: GLT-211-7-1 Issue 1.9 Author: MG/NJ Date: 06/04/2016 PAGE 19 www.acornfiresecurity.com...
  • Page 21: Loop Mode - Maximum Loop Length Recommendations

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 7.3 LOOP MODE - MAXIMUM LOOP LENGTH RECOMMENDATIONS Some care must be taken when calculating the appropriate cable gauge for the system. The main limitation is that during an alarm condition (maximum current draw), the voltage at all devices must be at least 17 Volts with at least 5V of superimposed data signal.
  • Page 22: Sounders

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 8 SOUNDERS The ID2 has two conventional sounder circuits on board. 9. AUXILIARY OUTPUTS 9.1 Auxiliary output wiring Auxiliary Fire Relay (AUX): This is a SELV volt free relay that operates in the alarm condition. It can be connected to emergency lights, local fire fighting equipment such as sprinkler systems, magnetic door holders, air conditioning shut off, etc.
  • Page 23: Field Device Termination

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 10. FIELD DEVICE TERMINATION 10.1 Terminating the wiring Figure 6: Cable connections All cables entering the enclosure should have cable glands, which will prevent unwanted openings in the enclosure. The Zone circuits should be connected to the appropriate connector block on the Termination PCB.
  • Page 24: Other Connections

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 11 OTHER CONNECTIONS 11.1 Repeater connection The ID2 has an RS485 connection for a serial repeater. The repeaters have full control. Up to 2 repeaters can be powered from the Aux24V DC output on the panel. If 3 or more are to be connected, then they must be powered from external 24V power supplies.
  • Page 25: Configuring The Id2 Fire Alarm Panel

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 12. CONFIGURING THE ID2 FIRE ALARM PANEL ID2/8 Zone Fire Alarm Panel System Normal 12.1 CONFIGURING THE ZONES 24-09-2012 09:35 Devices Found 12.1.1 FROM A BLANK INFINITY ID2 PANEL 1.
  • Page 26: Labelling The Panel And Zones

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 12.3 Labelling the Panel and Zones Panel / Zone Text 1. To add a Zone label, go to engineer menu 1and select option 2Panel / Zone Text. Panel Select option 1 to enter the panel name or customer name Zones Select option 2 to enter the zone text (i.e.
  • Page 27: Setting Individual I/O Unit Operation - Relay

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N These are the Triggers that will cause the I/O`s relay to operate EG the option ZONAL DETECTOR would cause the I/O`s relay to operate if there is an alarm from a Detector in its Zone.
  • Page 28: Configuring Alarm Output Resound Operation

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 12.8.5 CONFIGURING ALARM OUTPUT RESOUND OPERATION Alarm Resound Some installations require the sounders to operate in a certain way to new alarms if the Any New Alarm sirens have been silenced. To Access the settings, go to Engineer menu 1 / Config alarms / Resound .
  • Page 29: Alarm Verification

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 13 ALARM VERIFICATION The ID2 includes an option to use alarm verification. It is intended for use in apartments, and similar buildings, where it is desirable that an alarm from a smoke detector from one apartment (or area) would need to be confirmed before the whole system goes into alarm.
  • Page 30: Restoring The Panels Default Settings

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 14 RESTORING THE PANELS DEFAULT SETTINGS Because the ID2 allows several configuration changes, we have also included Misc Settings an option to reset the panel back to its default operation. From Engineer Menu 2, 1: Language Select Option 6 (Misc).
  • Page 31: Viewing Panel Information

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 15 VIEWING PANEL INFORMATION 15.1 Menu Structure To help locate the different features available, the menu structure of the ID2 panel is shown here. MENU LAYOUT MAIN MENU SUB MENU 1 SUB MENU 2 DESCRIPTION...
  • Page 32: Viewing Device Status

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 15.2 Viewing device status On the ID2, all Zone devices can be viewed from the Main Menu, or viewed & edited from Engineer Menu 1. Enter Engineer menu 1 as described above, and select option 1 Call-Pt (ID Device) Normal...
  • Page 33: Using The Event Log

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 15.4 Using the event log The ID2 has a 1000 entry event log. In the event of the log View Event Log being full, it will wrap around, and overwrite the earliest entries. 1: Alarms 4: All The event log can be viewed through Configuration Menu 1 by...
  • Page 34: The Fire Alarm Condition

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 16. THE FIRE ALARM CONDITION 16.1 Viewing a fire alarm event The way the ID2 panel shows fire alarm information has been changed slightly from previous versions of the panel.
  • Page 35: Disablement

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 17. DISABLEMENT On the ID2, there are 2 disablement options. A whole zone of devices can be disabled, or an individual device in a zone can be disabled. Both types of disablement can be used at the same time if required. Note that when there is any type of disablement present, line 3 of the “System Normal”...
  • Page 36: Device Disablement

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 17.3 Device disablement The ID2 panel can also disable individual devices (detector, Optical Normal call point, sounder or interface). To do this, enter ENGINEER Device Disabled MENU 1 and select ID DEVICE. Select the required device, them Zone:01 Lp:1 Ad:016 press GENERAL DISABLEMENT button.
  • Page 37: Test Mode

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 18. TEST MODE 18.1 Why use test mode To aid commissioning and assist routine maintenance check, a silent, non-latching ‘one man test’ facility is available. When a detector or manual call point is triggered on any zone in Test, the Device will light it`s LED, When the smoke has cleared, or the call point has been reset, the LED will turn out.
  • Page 38: General Fault Finding

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 19. GENERAL FAULT FINDING On the ID2 panel, Faults are divided into 2 types, “Faults” and “Device Faults”. Device Faults are any fault associated with a particular Device on the system. Faults are everything else, EG, power supply etc. In the event of multiple faults, the Faults are grouped together first, followed by the device faults.
  • Page 39: Supply Faults

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 19.4 Supply faults FAULT MESSAGE Caused by Remedy BATTERY FAULT Loss of Battery power Check “battery fuse 2A” is intact. Check that battery connections are secure POWER SUPPLY FAULT Loss of Mains power Check that main power is present.
  • Page 40: System Fault

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 19.7 System fault A system fault is an abnormal microprocessor running condition due to various unexpected phenomena. This will result in the panel attempting to correct itself. Should this fault occur, the System Fault LED, General Fault LED, General Fault relay and fault internal buzzer will be constantly active until the control panel is reset.
  • Page 41: Standby Battery Calculation

    Zeta Fyreye MKII Input Unit 1.0 mA 3.6 mA Zeta Fyreye MKII Input Output Unit 1.0 mA 3.6 mA Zeta Fyreye MKII Input Output Unit – mains switching 1.3 mA 2.9 mA Zeta Fyreye MKII Sounder Control Module 0.6 mA 0.8 mA Zone Fyreye MKII Zone Monitor Unit 3.5 mA...
  • Page 42: Example Battery Calculation

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 20.3 Example battery calculation A system comprises of a 4 zone Infinity ID2 panel, with 10 sounder-flasher bases, 1 call point, 1 Wall sounder flasher (xtratone), and one I/O per zone and the required standby is 24 hours. It will need to operate in alarm for ½...
  • Page 43: Pcb Termination Connections

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 21. PCB TERMINATION CONNECTIONS. Connection No Description 1- 8 Zone 1- 8 Connection for zone wiring Sounder circuit 1 Connection of conventional sounders Sounder circuit 2 Connection of conventional sounders Fault Relay Volt free relay.
  • Page 44: Specifications

    www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 22 SPECIFICATIONS 22.1 Enclosure specifications DESCRIPTION VALUE ENCLOSURE SIZE 369 x 310 x 113 mm TOP CABLE ENTRIES 15 x 19mm DIA ENTRIES 22.2 Electrical specifications ELECTRICAL DESCRIPTION MINIMUM NOMINAL MAXIMUM...
  • Page 45 www.acornfiresecurity.com INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N Installation Manual Modification History ISSUE DATE CHANGES 22/1/2013 Initial Release (Section 16.5 coloured white (“deleted”) – waiting software update) Corrected enclosure dimensions // Added max loop length // Added SndSmoke and SndHeat to device list // Added I/O Panel Link Information // Updated software version in header 23/3/1013 Re-write section 16.5 (viewing test mode during alarm)