Ups Specifications; Conformity And Standards; Ups Environmental; Ups Mechanical Characteristics - Emerson Liebert NX 480V User Manual

40-120kva, 480v, 60hz
Table of Contents

Advertisement

5.0
UPS S
PECIFICATIONS
These specifications describe requirements for the Liebert NX UPS.
5.1

Conformity and Standards

The UPS has been designed to conform to the following standards:
• IEEC 61000-4-5
• ASME
• CSA 22.2, No. 107.1
• FCC Part 15, Class A
• ISO 9001
• National Electrical Code (NFPA-70)
• NEMA PE-1
• OSHA
• UL Standard 1778
The UPS system has UL and c-UL approval.
5.2

UPS Environmental

The UPS is designed to operate under the following environmental conditions without damage or deg-
radation in electrical operating characteristics:
Table 6
Environmental characteristics
Rated Power
Operating Temperature, UPS
Optimal Operating Temperature, Battery
Relative Humidity
Acoustical Noise, dBA at 39 in. (1m)
Altitude of Operation
Storage-Transport Temperature, UPS,
Storage-Transport Temperature, Battery
5.3

UPS Mechanical Characteristics

Table 7
UPS mechanical characteristics
Width, in. (mm)
Depth, in. (mm)
Height, in. (mm)
Heat Dissipation, BTU/H (kWH)
3
Airflow, CFM (m
Cable Entry
Color
Protection Grade (with open/closed front doors)
Weight, lb (kg)
Parameter
/h)
40kVA
60/80kVA
100/120kVA
32°F to 104°F (0°C to 40°C)
68°F to 86°F (20°C to 30°C)
0 to 95%, non-condensing
62
62
≤1000m per IEC 62040/3
-4°F to 158°F (-20°C to 70°C)
-4°F to 86°F (-20°C to 30°C)
80kVA
120kVA
23.6 (600)
38 (965)
78.5 (2000)
5200 (1.52)
5500 (1.61)
1760 (2990)
1668 (2834)
Bottom or Top
Black (Z-0350)
IP 20
1290 (585)
1422 (645)
33

UPS Specifications