Specifications; Table 11 Liebert Nxl Ups Specifications - Emerson Liebert NXL Installation Manual

625-1100kva, 1.0pf, 60hz, three-phase, single-module & multi-module
Table of Contents

Advertisement

5.0
S
PECIFICATIONS
Table 11
Liebert NXL UPS specifications
Model Size
Input Parameters
Input Voltage to Rectifier, VAC
Input Voltage to Bypass, VAC
Permissible Input Frequency Range, Hz
Reflected Input THDi, Nominal Voltage, Full Load, %
Battery & DC Parameters
Minimum End of Discharge Voltage, VDC
DC Ripple Voltage in Float & Const V Ch. Mode, %
Temperature Compensated Battery Charging
Output Parameters
Output Voltage Regulation, %
Output Voltage Regulation (100% Unb. Load)
Output Frequency Regulation, %
Output THDv Linear Load at Nominal Voltage, %
Output THDv at Nominal Voltage
Including a 100kVA Non Linear Load per EN 62040-3,
Capacity to Handle High Crest Factor Load
Capacity to handle Step Load, %
Step Load Transient Recovery (linear loads), %
Unbalance Loads Current Capacity
Capacity to Handle Leading PF Load
Input Voltage Range, VAC
Input Frequency, Hz
Power Walk-In, sec
Bypass Neutral Current
Battery Type
Nominal Battery Bus, VDC
Battery Float Voltage, VDC
Inverter Type
Output Power, kW
Output Voltage, VAC
Output Frequency, Hz
%
at 0.95 Lead
at 0.9 Lead Subject to 12.5% kW derate or same Rating and 10°C Temp. Derate
Voltage Displacement, ° el
Compliance to FCC Class-A
Overload Conditions, % FL
625kVA
480V 3-phase, 3-wire
575V 3-phase, 3-wire
600V 3-phase, 3-wire
480V 3-phase, 3-wire or 4-wire
575V 3-phase, 3-wire or 4-wire
600V 3-phase, 3-wire or 4-wire
+10% to -30%
1 to 30 (selectable) in 1 sec. Increment
up to 1.7 times full-phase current
VRLA (Valve Regulated Lead Acid) or FLA (Flooded Lead Acid)
384V (for VRLA / Flooded Lead Acid)
<1 (RMS value) < 3,4% Vpp
Optional (with temperature probe)
IGBT-based Sine-Sine PWM Controlled
625
480V 3-ph, 4-wire
575V 3-ph, 4-wire
600V 3-ph, 4-wire
< 1% (3-phase RMS average)
< 2% (3-phase RMS average)
2.5% (max)
0-100 or 100-0
Within 5% peak-to-peak in one line cycle.
100% of nominal phase current
Subject to Max. kW rating
120° ±1° el (with 100% unbalanced load)
See Figures 51, 52 and 53
63

Specifications

1100kVA
60
55 to 65
<5%
480V
540V
1100
60
± 0.1
<2%
3:1
Standard