Messages; Table 36 Ups Status Messages - Emerson Liebert NX 480V User Manual

40-120kva, 480v, 60hz
Table of Contents

Advertisement

A
A - UPS S
PPENDIX
Table 36 shows all event messages as they appear in the current status area of the LCD and in the
history log, along with a description and recommended actions, if any. For further information on the
current status area and the history log, see 2.11 UPS Status Messages.
Table 36
UPS status messages
Event Message
Inverter Comm. Fail
Rectifier Comm. Fail
Parallel Comm. Fail
Battery Overtemp.
Ambient Overtemp.
Replace Battery
Battery Low Pre-warning
Battery End of Discharge
Mains Volt. Abnormal
Mains Undervoltage
Mains Freq. Abnormal
Rectifier Fault
Input Inductor Overtemp.
Rectifier Overtemp.
Charger Fault
Control Power 1 Fail
Mains Phase Reversed
Rectifier Overcurrent
Soft Start Fail
M
TATUS
ESSAGES
Description / Suggested Action (if any)
The RS-485 communication between internal monitor and inverter has failed. Contact Liebert
Global Services at 800-543-2378 for assistance.
The RS-485 communication between internal monitor and rectifier fails. Contact Liebert Global
Services at 800-543-2378 for assistance.
The CAN communication between different UPS units within a parallel system has failed.
Check if there are some UPS units not powered on in the parallel system. If so, power on these
UPS units and check if the alarm disappears.
Press Fault Clear push button.
If alarm does not clear, contact Liebert Global Services at 800-543-2378
The battery temperature is over limit. Check the battery temperature and ventilation
The ambient temperature is over limit. Check the ventilation of UPS room.
Battery should be replaced. Contact Liebert Global Services at 800-543-2378 for assistance.
Before the end of discharging, battery under-voltage pre-warning should occur. After this pre-
warning, battery should have the capacity for 3 minutes discharging with full load. The time is
user configured from 3 to 60 minutes.
Shut down the load in time to prevent damage to equipment and data.
Inverter turned off due to low battery voltage.
Check the utility failure and try to recover it.
Mains voltage exceeds the upper or lower limit and results in rectifier shutdown.
Check the input line-to-line voltage amplitude of rectifier.
Mains voltage is undervoltage 288V~384V line to line voltage with derated load.
Check the input line-to-line voltage amplitude of rectifier.
Mains frequency is out of limit range and results in rectifier shutdown.
Check the rectifier's input voltage frequency
Contact Liebert Global Services at 800-543-2378 for assistance.
The temperature of rectifier inductor of rectifier common mode inductor is too high to keep the
rectifier running.
Check the ambient temperature and ventilation; contact Liebert Global Services at
800-543-2378 for assistance.
The temperature of the heat sink is too high to keep the rectifier running.
The UPS can recover automatically. Check the environment and ventilation.
The charger has a fault. Contact Liebert Global Services at 800-543-2378 for assistance.
Control Power 1 has failed or has been lost. Contact Liebert Global Services at 800-543-2378
for assistance.
Input phase sequence is inverse. Contact Liebert Global Services at 800-543-2378 for
assistance.
The current of rectifier is over limit. Contact Liebert Global Services at 800-543-2378 for
assistance.
Rectifier could not start due to low DC bus voltage. Contact Liebert Global Services at
800-543-2378 for assistance.
93
UPS Status Messages