Failure to observe this could result in personnel safety risk, equipment malfunction and invalidation of warranty. The NXr UPS is only used for commercial or industrial purpose and cannot be used as life support equipment. This is a C2 type UPS product. In a domestic environment, this product may cause radio frequency interference, in which case, the user may be required to take additional measures.
Page 4
Battery voltage higher than 400Vdc All the battery physical maintenance and servicing procedures need special tools or keys and should be carried out only by trained personnel. Take special care when working with the batteries associated with this UPS. When the batteries are connected together, the battery terminal voltage exceeds 400vdc and is potentially leathal.
Page 7
2.5 Battery Recycling ..............................20 2.6 Connection Of External Battery Circuit-Breaker (BCB ..................20 Chapter 3 Installation Of Multiple UPS cubicles ........................ 22 3.1 Overview ................................22 3.2 1 + N Parallel System ............................22 ...
Page 8
5.2.1 Start Screen ............................. 34 5.2.2 Primary Screen ............................34 5.2.3 Default Screen ............................35 5.3 Selecting Language ............................35 5.4 Changing The Current Date And Time ........................ 35 5.5 Control Password ..............................35 5.6 Detailed Description Of Menu Items ........................
Page 9
8.8 Efficiency, Heat Losses And Air Exchange ......................54 Appendix 1 Option List ..............................55 Appendix 2 List Of Abbreviations ............................56 ...
Chapter 1 Installation Of UPS Module Chapter 1 Installation Of single UPS cubicle This chapter introduces the installation of Emerson NXr 30kVA ~ 200kVA UPS (hereinafter referred to as UPS) module, including the initial check, location selection, positioning, external protective device and cable connection.
During storage, periodically charge the battery according to the battery manufacturer instructions. In the charge process, temporarily connect the UPS to the mains and activate the battery for the time required for recharging the battery. NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
UPS base. If the UPS is mounted on raised floor, a suitable pedestal should be designed, which should be able to bear the UPS weight. When designing the pedestal, refer to the bottom view in Figure 1-1 and Figure 1-2. NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
Page 13
Chapter 1 Installation Of UPS Module Front view Side view Anchor hole Top view Bottom view A amplified view ~ Figure 1-1 30kVA 160kVA UPS installation dimensions (unit: mm) NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
External circuit breakers or other protective devices must be fitted at the input AC supply of the UPS. This section provides a general guide for qualified installation engineers. The installation engineers should have the knowledge of the local wiring regulations on the equipment to be installed. NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
380V 400V 415V 380V 400V 415V Bolt Bolt Torque (N.m) (N.m) 150, 160 90 、 100 30-B Note: 1. Input mains current for common rectifier and bypass AC input. NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
Once the equipment has been finally positioned and secured, refer to Figure 1-3 to connect the power cables as described in the following procedures: NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
Page 17
2. Open the UPS door and remove the protective cover at the lower part in the front to gain access to the power terminals, as shown in Figure 1-4 to Figure 1-6. NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
Page 18
Chapter 1 Installation Of UPS Module Figure 1-4 30kVA (NXr 30K-B) UPS power terminals NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
Page 19
2. Bypass input: bA, bB, bC, mN 3. UPS output: oA, oB, oC, oN 4. Battery input: + , - , N 5. Earth: PE Figure 1-6 200kVA UPS power terminals NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
Page 20
(+) to (+) and (–) to (–), but disconnect one or more battery cell links in each tier. Do not reconnect these links and do not close the BCB before authorized by the commissioning engineer. 6. For frequency converter applications ensure the bypass links are removed. 7. Replace the protective cover. NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
+12V power J8.1 BAT_IN Internal battery temperature detection J8.2 +12V +12V power J8.3 BAT_OUT External battery temperature detection J8.4 Power ground Note*: Activating this feature turns off the battery charger NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
IN_S J9.2 shorted to J9.4 when Internal maintenance switch is closed J9.3 EXT_OUT External output isolator (EOI) Aux Contact closed to J9.4 when EOI is closed. J9.4 Power ground NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
Pins 1 and 2 of J10 are supplied factory-shorted. If the UPS EPO function is not used, pins 1 and 2 of J10 must remain shorted and pins 3 and 4 of J10 must remain open . NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
For details, refer to the user manuals of the each specific network interface card. Service ports J2 and J3: Parallel connection ports - used for control of two or more NXr UPS cabinets operating in parallel. J4: Load Bus Synch (LBS) interface - used to synchronize the outputs of two NXr UPS systems operating in dual bus mode.
Batteries of different brand, model and age should nottbe used together. Except for the NXr 30K-B model that contains internal batteries, all UPS batteries are located external to the UPS cabinet and is normally housed in a battery cabinet or located on stands/racks.
12) Before connecting or disconnecting the battery connection cables, please cut off the charging power. 13) Check if the battery has been unexpectedly earthed. If yes, remove the earth power. Contact with any part of the earthed battery may cause electric shock. NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
8. Refer to Figure 2-1 and Figure 2-2 for the battery cable connection. 9. For NXr 30K-B UPS, it is required to install the factory supplied separators between the two rows of batteries on each layer of the battery compartment, as shown in Figure 2-2.
Figure 2-2 Internal battery cable connection (NXr 30K-B) 2.4 Battery Maintenance The battery supplied by Emerson complies with the safety requirements of IEC 62040-1:2008. For the battery maintenance and maintenance precautions, refer to the relevant manual provided by the battery manufacturer and observe applicable local regulation e.g.
Emerson, please consult the local customer service center or sales office of Emerson. If the customer refuses to accept this special note or does not use the disused battery recycling system of Emerson. Emerson will not undertake any environment responsibility caused by the improper disposal of the disused battery products.
Page 30
Auxiliary Bypass module contactor BCB control board UHW241C2 X101 X102 X108 +12V +12V BAT -T BAT-T GND2 GND1 Figure 2-6 Connections between UPS, BCB and BCB control board (option) NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
The basic installation steps of parallel system are the same as those of the single UPS cubicle. The following sections describe the differences between the parallel system installation and single UPS installation. NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
UPS output switches and maintenance bypass must be installed, as shown in Figure 3-2, to facilitate maintenance and system testing. Figure 3-2 Typical “1+N” system schematic diagram (with common input, separate battery and output/bypass distribution cabinet) NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
. Note The length and specification of power cables including the bypass input cables and UPS output cables should be the same. This facilitates load sharing in bypass mode. NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
Be sure to verify the reliable cable connection before starting up the system. UPS 1 UPS 3 UPS 4 UPS 2 Figure 3-5 Connection of parallel control cables of 1+N parallel system NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
3.3.4 Control Cable For NXr-to-NXr dual bus system, connect the optional LBS cables between the LBS ports (J4) of the two parallel systems, as shown in Figure 3-8. The LBS port (J4) is provided on the front panel of the bypass module, as shown in Figure 3-6.
Page 36
Chapter 3 Installation Of Parallel System UPS 1 UPS 2 UPS 3 UPS 4 Bypass module Bypass module Bypass module Bypass module LBS cable LBS cable Figure 3-8 Connection of typical dual bus system NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
(no-break) load transfer between the inverter output and static bypass line. The synchronization between the inverter output and static bypass is achieved through the inverter control electronics, which make the NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
The UPS is an on-line, double-conversion, reverse-transfer UPS that permits operation in these modes: Normal mode Battery mode (“stored energy mode”) Automatic restart mode Bypass mode Maintenance mode (manual bypass) Parallel redundancy mode NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
The boost charge voltage can be set as required by the type of battery. For valve-regulated lead-acid (VRLA batteries, the maximum boost charge voltage should not exceed 2.4V/cell. 3. Float charge. NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
The battery disconnect device alarm occurs when the battery disconnect device disconnects. The external battery connects to the UPS through the external BCB. The BCB is manually closed and tripped by the UPS control circuit. NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
State Description Solid green Rectifier in normal operation Flashing green Mains input normal, but rectifier not operating Rectifier indicator Solid red Rectifier fault Rectifier not operating, mains input abnormal NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
The operator control and display panel provides an LCD and five menu keys (F1 ~ F5). The menu keys are described in Table 5-5. Table 5-5 Menu key description Function 1 Escape HOME Left Right Enter Function 2 Down NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
The functions of the menu keys F1 ~ F5 for the current screen are shown by self-explanatory icons in the keypad window as appropriate. From any menu on the primary screen, pressing the F1 key returns to the Output menu。 NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
This password provides access to UPS and battery test functions. 5.6 Detailed Description Of Menu Items The description that follows refers to the LCD primary screen shown in Figure 5-3. NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
Page 45
Displays the alarm history. For the list of the alarms that may be displayed on Records (alarm history) the LCD on the UPS operator control and display panel, refer to Table 5-9 Language (language option) Provides 12 optional LCD languages NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
This prompt appears to require your confirmation. Cancelling the test will ends cancel the test and transfers the UPS to Normal mode System self test finished, everything is No action required NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
UPS. If the bypass voltage and frequency are abnormal, check the external bypass supply. 4. If the mains is likely to trigger this alarm frequently, the bypass limits can be changed to a wider NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
Page 48
The neutral line of the AC input mains is not detected The battery ground fault option has detected a battery ground fault. Contact the local customer service Battery ground fault center of Emerson to inspect the battery installation NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
Page 49
Rectifier software being updated Inv Flash Update Inverter software being updated Monitor Flash Update Monitoring software being updated Bypass Flash Update Bypass software being updated LBS abnormal LBS abnormal NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
The UPS provides a maintenance switch only (silkscreen: MAINTAIN CB), as shown in Figure 6-1 to Figure 6-3. The user needs to provide the other switches. Maintenance switch Figure 6-1 Location of maintenance switch of 30kVA (NXr 30K-B) UPS NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
Chapter 6 Operating Instructions Maintenance switch Figure 6-2 Location of maintenance switch of 30kVA (NXr 30K) ~ 160kVA UPS Maintenance switch Figure 6-3 Location of maintenance switch of 200kVA UPS 6.2 UPS Startup Procedures It is assumed that the installation is complete, the system has been commissioned by authorized personnel, and the external power isolators are closed.
At this point, the LCD starts up, and the battery indicator starts flashing in green color. After the rectifier has operated normally for 30s, the battery indicator stops flashing and becomes solid green. 电池启动按钮 Battery start button Figure 6-4 Location of battery start button Note NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
1. If you need to maintain a faulty module, wait for 10min to let the internal DC bus capacitor fully discharge before removing the faulty module for maintenance. 2. When the UPS in operating in maintenance mode, the neutral line is still energized. Therefore, only qualified personnel shall NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
4. Open the output switch of the UPS. 6.6 Isolation Procedures (Of One UPS In A Parallel System) Caution The following procedures will switch off all power to the load. NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
In the case of a mains failure, the UPS draws power from the battery system to supply the load until the batteries are depleted. When the UPS reaches its end of EOD threshold, it shut will down. The UPS will automatically restart and enable output power: NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
UPS. 2. If you need to maintain a faulty module, wait for 10min to let the internal DC bus capacitor fully discharge before removing the faulty module for maintenance. NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
If the UPS has been transferred to bypass, press and hold the INVERTER ON button for two seconds to start up all power modules. 7.1.3 Service Procedures Of Bypass Module Provided that the UPS is in normal mode, and that the bypass is normal: NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
5. Tighten the fixing screws of the fixing bar on the other side. Fixing screw Fixing bar Fixing bar Air filter Figure 7-1 Replacing air filter of 30kVA ~ 160kVA UPS NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
Page 59
Chapter 7 Service Fixing screw Fixing bar Fixing bar Air filter Figure 7-2 Replacing air filter of 200kVA UPS NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
2.4 (selectable from 2.30V/cell to 2.40V/cell) Constant current and constant voltage charge mode Programmable automatic trigger or inhibit of boost mode Battery 13.5 22.5 charging power and max charging 14.7 current (adjustable) NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
Current rating of neutral 1.7 × In cable Frequency 50/60 Synchronous transfer: ≤1 Transfer time (between Asynchronous transfer (default): 15 (50Hz), 13.3 (60Hz); or 40, 60, 80, 100 bypass and inverter) selectable NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
Page 63
Heat losses & air exchange Normal mode No load Maximum forced air cooling (front L/sec intake, rear exhaust) Note: 400Vac input and output, battery fully charged, full-rated linear load NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
Applicable to 30kVA (NXr 30K) ~ 100kVA UPS Bypass load sharing inductor UF-NRBYPCK-160 02354042 Applicable to 120kVA ~ 160kVA UPS Bypass load sharing inductor UF-NRBYPCK-200 02354314 Applicable to 200kVA UPS NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...
Page 65
MCCB Moulded-case circuit breaker Center tap Battery circuit breaker Load bus synchronizer Pulse width modulation Full digital control Static transfer switch VRLA Valve-regulated lead-acid liquid crystal display Electromagnetic compatibility NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual...