Specifications; Table 7 Ups Specifications-5000, 6000, 8000 And 10,000 Models - Emerson Liebert GXT3 208V 5000-10000V User Manual

Table of Contents

Advertisement

12.0 S
PECIFICATIONS
Table 7
UPS specifications—5000, 6000, 8000 and 10,000 models
Model Number
Model Rating
Dimensions, Rack Mount, W x D x H
Shipping, in. (mm)
Weight lb (kg)
Input AC Parameters
Nominal Operating Frequency
Factory Default VAC
L1-L2 Factory Default Input Phase Angle
Allowable Input Phase Angle
Factory Default L1-N, L2-N VAC
User Configurable L1-N, L2-N VAC
Input Frequency w/o Battery Operation
Input Power Connection
L1-N, L2-N Maximum Allowable VAC
Output AC Parameters
Factory Default VAC
L1-L2 Factory Default Output Phase Angle
Allowable Output Phase Angle
Factory Default L1-N, L2-N VAC
User Configurable L1-N, L2-N VAC
L1-N, L2-N, Operating Load Range
>200% (impact load)
Bypass Protection Limits
Disable Bypass Operation
Re-Enable Bypass Operation
Disable Bypass Operation
Environmental
Operating Temp, °F (°C)
Storage Temp, °F (°C)
Relative Humidity
Operating Elevation
Agency
GXT3-5000RT208 GXT3-6000RT208 GXT3-8000RT208 GXT3-10000RT208
4000W/5000VA
Unit, in. (mm)
16.9 x 26.1 x 6.8 (430 x 662 x 173)
26.1 x 33.1 x 13.2 (662 x 842 x 336)
Unit, lb (kg)
Shipping, lb (kg)
120/208VAC at 120 degrees
120, 180, 240 degrees, auto-sensing on application of alternating current
100/110/115/120/127 VAC (can be modified with configuration program)
120, 180, 240 degrees, auto-sensing on initial application of input AC
105% to 130%
131% to 150%
151% to 200%
If input voltage returns to within ±10% of nominal output voltage
32 to 104 (0 to 40); see Table 9 - Operating temperature parameters
Audible Noise less than 55dBA at 3.2ft. (1m) rear; less than 50dBA at 3.2ft. (1m) front and sides
Safety
UL 1778, c-UL Listed (suitable for computer room applications)
RFI/EMI
Surge Immunity
Transportation
4800W/6000VA
56.2 (25.5)
70.5 (32)
50 or 60Hz (Factory Default is 60Hz)
120 degrees
(Restrictions for L-N voltages other than 120VAC)
120 VAC nominal
40 - 70 Hz
Hardwire Terminal Block 3W + G (L-L-N-G)
150VAC
120/208VAC @ 120 degrees
120 degrees
120VAC nominal
100/110/115/120/127VAC, ±2%
1 Minute
10 seconds
1 second
At least 5 cycles
If input voltage exceeds ±15% of the nominal voltage
When the input frequency prevents synchronous operation
5 to 122 (-15 to 50)
0% to 95%, non-condensing
Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
FCC Part 15, Subpart B, Class A, FCC Class A
IEEE/ANSI C62.41 Category A & B
ISTA Procedure 1A
38

Specifications

7200W/8000VA
9000W/10000VA
16.9 x 26.5 x 10.3 (430 x 672 x 261)
24.1 x 32.8 x 16.7 (612 x 832 x 424)
78.3 (35.5)
92.6 (42)
120/208VAC at 120 degrees
120 degrees

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

6000rtl630Liebert gxt3 6000rtl630

Table of Contents