General
The Liebert NX UPS uses intelligent and reliable
decentralized technology to achieve parallel
operation of two modules of the same rating.
The 1+1 system is used to:
• Increase the reliability of the system to ensure
adequate power supply to the critical load.
• Increase serviceability and allow the execution of
maintenance operations and reparations without
affecting the ordinary operating conditions of the
system (depending on the redundancy level).
CAUTION
!
An external maintenance cabinet is
strongly recommended to maintain the
power supply to load in case of complete
maintenance.
Conditions for Parallel System
1. Each UPS module should have the same rating,
the same firmware and hardware version.
2. Each UPS module must have the same bypass
source.
3. The outputs of all UPS modules are connected
altogether.
4. The main inputs can be from different sources,
but the phase rotation sequence of main inputs,
bypass inputs and outputs must be correct and
the same.
1+1 System
+
5. The parallel logic cable and load sharing cable
must be connected in a ring correctly (see
Figure 2).
Features of Parallel System
1. The hardware and firmware for parallel UPS
module operation is standard in the Liebert NX,
and the configuration can be set up by changing
the settings in configuration software.
2. It is easy to install the parallel cables in a ring,
providing high reliability and redundancy. And
the intelligent paralleling logic provides the user
with maximum flexibility. For example, shutting
down or starting up the UPS modules in the
parallel system can be done in any sequence. If
an overload transfer occurs, the whole system
can recover automatically from bypass mode
after the overload is cleared.
3. The total load of the parallel system can be
queried from each module's LCD screen.
4. Optional monitoring background software can
treat the entire parallel system as a big single-
module UPS, and provide corresponding
management. It can also get the information for
all modules by connecting to just one of the
modules.
1

Advertisement

loading

Summary of Contents for Emerson Liebert NX

  • Page 1 Product Specification/Installation Sheet General 5. The parallel logic cable and load sharing cable must be connected in a ring correctly (see The Liebert NX UPS uses intelligent and reliable Figure 2). decentralized technology to achieve parallel Features of Parallel System operation of two modules of the same rating.
  • Page 2 Figure 1 '1+1' System block diagram Supplied by Others Input Utility Input Utility Supply A B C Supply A B C UPS1 UPS2 Rectifier Rectifier SW1-C SW1-C Fuse Fuse Static Static Switch Switch Charger Charger Battery 1 Battery 2 SW1-D SW1-D Inverter Inverter...
  • Page 3 Refer to the instructions in Conditions for Parallel System on page 1. Protective Devices 1 & 2 - UPS Unit Refer to the instructions in the Liebert NX 3 - Parallel Connection Board installation manual, SL-25215. 4 - Interconnecting Cables...
  • Page 4: System Startup

    Emergency Power Off (EPO) • Parallel system redundant UPS units: Set the number of redundant UPS modules. This will The external emergency stop facility is identical to prevent the system from transferring to Bypass if that described for the single unit installation—that a fault condition occurs on the Master UPS in the an individual emergency stop button is provided for parallel system.