Ups Status Messages; Figure 48 Current Status And History Log Records - Emerson Liebert NX 480V User Manual

40-120kva, 480v, 60hz
Table of Contents

Advertisement

8.11

UPS Status Messages

The Liebert NX displays status changes as they occur in the current status window of the LCD,
then stores that data in the history log, as shown in Figure 48.
• Current Status Window: The status messages are displayed chronologically and include the
date and time of the events. Three status messages are visible in the window at a time. To see
other messages, use the navigation keys to scroll up or down the list. A status message remains in
the current status area of the LCD until the status changes, when it is moved to the history log.
• History Log: When a record moves to the history log, the time the status changed is recorded.
The history log can hold up to 512 records. History log records may be viewed by accessing the
Records menu.

Figure 48 Current status and history log records

Current
Status
Messages
See Appendix A for a complete list of status messages, along with a description and any recom-
mended actions.
2007-01-12
Liebert NX
Single
80KVA-3X3
Battery
History
Inverter in setting
2003-01-21
12 :21:12
2003-01-21
12 :21:12
UPS shutdown
2003-01-21
12 :21:12
2003-01-22
12 :30:16
Bypass abnormal
2003-01-21
12 :21:12
2003-01-21
12 :30:16
Input disconnect closed
Output disconnect closed
Bypass disconnect open
F1
F2
F3
Operator Control and Display Panel
12:30:36
Normal
Language
01-12 12:30
01-12 12:30
01-12 12:30
?
F4
HELP
66
History Log
(records
menu)