Table 8-1: Ups Specifications; Table 8-2 Power Distribution Specifications - Emerson GXT4-5000RT230 User Manual

Liebert gxt4 230 v, 5000 va – 10,000 va
Hide thumbs Also See for GXT4-5000RT230:
Table of Contents

Advertisement

Specifications
Model #
Bypass Protection Limits
Disable Bypass Operation
Re-Enable Bypass Operation
Disable Bypass operation
Environmental
Operating Temperature, °C (°F)
Storage Temperature, °C (°F)
Relative Humidity
Operating Elevation
Audible Noise
Agency
EMI/EMC/C-Tick EMC
Radiated Susceptibility
Electrical Fast Transient
Surge Immunity
Transportation
Model Number
Amp Rating
Input Power Connection
Output Power Connection
Includes:
Input Branch Circuit
Breaker, Supplied by User
®
Liebert
GXT4
User Manual
Table 8-1
UPS specifications (continued)
GXT4-5000RT230
GXT4-5000RT230E
If input voltage exceeds ±15% of the nominal voltage
If input voltage returns to within ±10% of nominal output voltage
When the input frequency prevents synchronous operation
Up to 1000m (3281 ft) at 25°C (77°F) without derating
<55 dBA, at 1 meter from the rear <50 dBA, at 1 meter from the front or sides
Safety
ESD
Table 8-2
Power distribution specifications
PD2-CE6HDWRMBS
32 Amps
Single-phase (L-N-G) hard-wired, 6-10mm
Single-phase (L-N-G) hard-wired, 6-10mm
Two IEC320 C19 16A/250V Sockets
Six C13 10A/250V Sockets
Manual Bypass Switch with Indicator Lamps
32A
GXT4-6000RT230
GXT4-6000RT230E
0 to 40 (32 to 104) (no derating)
-15 to 50 (5 to 122)
0-95% non-condensing
IEC62040-1:2008 version, GS mark
IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6)
IEC/EN EN61000-4-2, Level 4, Criteria A
IEC/EN EN61000-4-3, Level 3, Criteria A
IEC/EN EN61000-4-4, Level 4, Criteria A
IEC/EN EN61000-4-5, Level 3, Criteria A
ISTA Procedure 1E
Four IEC320 C19 16A/250V Sockets,
Manual Bypass Switch with Indicator Lamps
54
GXT4-10000RT230
GXT4-10000RT230E
PD2-CE10HDWRMBS
63 Amps
2
(8-10AWG)
2
(8-10AWG)
Four C13 10A/250V Sockets
63A