Lcd Menus And Data Items; Figure 45 Menu Tree - Emerson Liebert NX 480V User Manual

40-120kva, 480v, 60hz
Table of Contents

Advertisement

8.8

LCD Menus and Data Items

The LCD menus provide access to the following categories of information and settings for the UPS.
Selecting a menu changes the information displayed in the UPS data items portion of the LCD. The
menu choices are listed below and described in detail in Table 19.
• Mains - view utility power input data: voltage, current, frequency and power factor
• TX Input - view input transformer voltages
• Bypass - view bypass data: voltage and frequency
• Output - view output data: voltage, current, frequency and power factor
• Load - view load data: load percent, output current, output power and crest factor (CF)
• System - view system data
• Battery - view battery characteristics—voltage, current, temperature and remaining time—and
messages when the battery is boost/float charging or disconnected
• Records - access the history log—displays all records in the log (newest records added at end)
• Language - select a language for LCD text (choices appear in the native language)
• Settings - configure UPS settings: adjust the display contrast, choose a format for date display,
set the date and time, set up the UPS for modem communications (baud rate, address, mode and
phone numbers to dial for alarm notifications) and change the password
• Command - start or stop a battery maintenance test, battery capacity test or system test
• Version - view firmware versions for the inverter, rectifier and software display board and the
model information for the UPS
Figure 45 shows a menu tree of the options available from the LCD menus.

Figure 45 Menu tree

Mains (input)
L-N current (A)
Frequency (Hz)
L-L voltage (V)
Power factor
Load
Sout (kVA)
Pout (kW)
Qout (kVAR)
Loadlevel %
Crest factor
Language
(Choices for
display)
TX Input *
Bypass
L-L voltage (V)
Frequency (Hz)
L-L voltage (V)
System
Sout (kVA)
Pout (kW)
Qout (kVAR)
Single unit, no
parallel data
Settings
Display contrast
Date format set
Date & time
Comm1 baud rate
Comm2 baud rate
Comm3 baud rate
Communication address
Communication mode
Callback times
Phone No.1
Phone No.2
Phone No.3
Command password
Operator Control and Display Panel
Output
L-N current (A)
Frequency (Hz)
L-L voltage (V)
Power factor
Battery
Battery voltage (V)
Battery current (A)
Battery temperature (°C)
Remain Time Min.
Battery boost charging
Battery float charging
Battery disconnected
Command
Battery maintenance test
Battery capacity test
System test
Stop testing
Freshening Charge
Stop Freshening Charge
Modem auto-answer enable
* When configured, input transformer voltages are
displayed on the front LCD. When not activated, the
values are hidden.
** When configured, output transformer voltages are
displayed on the front LCD. When not activated, the
values are hidden.
62
TX Output **
L-L voltage (V)
Records
(history log)
Version
UPS model
Monitor version
Rectifier version
Inverter version