Ups Specifications; Conformity And Standards; Ups Environmental; Ups Mechanical Characteristics - Emerson Liebert NX 10-30kVA Installation Manual

Liebert nx series 10-30kva, 208v, 60hz
Table of Contents

Advertisement

6.0
UPS S
PECIFICATIONS
These specifications describe requirements for the Liebert NX UPS.
6.1

Conformity and Standards

The UPS has been designed to conform to the following standards:
• IEEC1000-4-5
• ASME
• CSA 22.2, No. 107.1
• FCC Part 15, Class A
• ISO 9001
• National Electrical Code (NFPA-70)
• NEMA PE-1
• OSHA
• UL Standard 1778
The UPS system has UL and c-UL approval.
6.2

UPS Environmental

The UPS is designed to operate under the following environmental conditions without damage or deg-
radation in electrical operating characteristics:
Table 8
Environmental characteristics
Operating Temperature, UPS
Optimal Operating Temperature, Battery
Relative Humidity
Acoustical Noise, dBA at 39 in. (1m)
Altitude of Operation
Storage-Transport Temperature, UPS
Storage-Transport Temperature, Battery
6.3

UPS Mechanical Characteristics

Table 9
Mechanical characteristics
Width, in. (mm)
Depth, in. (mm)
Height, in. (mm)
Weight Without Inner Batteries, lb. (kg)
Heat Dissipation, BTU/H (kWH)
3
Airflow, CFM (m
Cable Entry
Color
Protection Grade (with open/closed front doors)
Rated Power
Parameter
UPS12-100 weight
UPS12-140 weight
/h)
10-30kVA
32°F to 104°F (0°C to 40°C)
68°F to 86°F (20°C to 30°C)
0 to 95%, non-condensing
54
≤1000m per IEC 62040/3
-4°F to 158°F (-20°C to 70°C)
-4°F to 86°F (-20°C to 30°C)
10kVA
15kVA
24 (600)
32.5 (825)
63 (1600)
450 (205)
450 (205)
954 (433)
954 (433)
1098 (498)
1098 (498)
2800 (0.82)
4200 (1.23)
384 (652)
558 (948)
Bottom or top
PMS 877
IP 20
38

UPS Specifications

20kVA
30kVA
550 (250)
550 (250)
1054 (478)
1054 (478)
1198 (543)
1198 (543)
5500 (1.61)
8300 (2.43)
522 (886)
834 (1417)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents