Battery Protection; Battery Undervoltage Pre-Warning; Battery End-Of-Discharge (Eod) Protection; Multi-Module System Procedures - Emerson Liebert NX 480V User Manual

40-120kva, 480v, 60hz
Table of Contents

Advertisement

9.7

Battery Protection

9.7.1

Battery Undervoltage Pre-Warning

Before the end of discharge, the Liebert NX displays a Low Battery pre-warning. After this pre-warn-
ing, the battery has the capacity for 5 minutes discharging with full load (default time). The Liebert
NX can be user-configured to display this warning from 3 to 60 minutes before end-of-discharge.
9.7.2

Battery End-of-Discharge (EOD) Protection

If the battery voltage is lower than the end-of-discharge voltage, the battery converter will be shut
down.
9.8

Multi-Module System Procedures

9.8.1

Isolating One Module in a Multi-Module System

1. Turn Off the inverter
2. Open External Output CB4 in Parallel Cabinet (see Figure 54).
The UPS enters Isolation Status automatically, parallel signaling and communication become
masked and output becomes inhibited.
3. Power Off the unit for maintenance.
4. Power On the unit.
5. Unit enters Test Mode by configuration software setting.
6. Diagnosis or testing.
7. The UPS exits Test Mode by configuration software setting.
Output becomes inhibited because of Isolation Status.
8. Return all switches to the Normal position.
9. Close External Output CB4 in Parallel Cabinet (see Figure 54).
The UPS exits Isolation Status automatically, parallel signaling and communication recovers,
output becomes enabled but interlocking works now.
10. Turn On inverter and join the parallel system.
76
Operating Instructions

Advertisement

Table of Contents
loading

Table of Contents