Battery Run Times; Table 35 Estimated Battery Run Time, Minutes - Emerson Liebert NX 480V User Manual

40-120kva, 480v, 60hz
Table of Contents

Advertisement

11.4

Battery Run Times

Table 35
Estimated battery run time, minutes
UPS Rating/Model
40kVA UPS
UPS12-100MR
UPS12-150MR
UPS12-210MR
60kVA UPS
UPS12-100MR
UPS12-150MR
UPS12-210MR
80kVA UPS
UPS12-100MR
UPS12-150MR
UPS12-210MR
100kVA UPS
UPS12-100MR
UPS12-150MR
UPS12-210MR
120kVA UPS
UPS12-100MR
UPS12-150MR
UPS12-210MR
Number of Cabinets
1
2
3
4
5
18
32
47
13
33
53
75
21
51
81
123
-
9
18
27
7
19
33
47
11
31
51
73
-
5
11
18
-
13
22
33
6
21
36
51
-
-
8
12
-
9
17
25
-
15
27
38
-
-
5
9
-
7
13
19
-
11
21
31
92