Using Intelligent Input Terminals; Input Wiring Examples - Hitachi L300P Series Instruction Manual

Three-phase input 200v class; three-phase input 400v class;
Hide thumbs Also See for L300P Series:
Table of Contents

Advertisement

4–10

Using Intelligent Input Terminals

Using Intelligent Input Terminals
Input Wiring
Examples
Intelligent terminals [1], [2], [3], [4] and [5] are identical, programmable inputs for general use.
The input circuits can use the inverter's internal (isolated) +24V field supply (P24) to power the
inputs. The input circuits connect internally to [PLC] as a common point. To use the internal
supply to power the inputs, use the jumper as shown. Remove the jumper to use an external
supply, or to interface to a PLC system (or other) that has solid state outputs. If you use an
external supply or PLC system, its power return must connect to the [PLC] terminal on the
inverter to complete the input circuit.
The following four input configurations are available to interface the inverter inputs to switches
or the outputs of another system, such as a PLC.
Sinking inputs,
internal supply
Jumpered for sinking inputs
(default for –xFE2 models)
Sourcing inputs,
internal supply
Jumpered for sourcing inputs
(default for –xFU2/–FR models)
Sinking inputs,
external supply
External
power supply
Sourcing inputs,
external supply
External
power supply
24VDC
+ –
common
P24
PLC
CM1
24VDC
+ –
common
P24
PLC
CM1
24VDC
+ –
common
P24
PLC
CM1
24VDC
+ –
common
P24
PLC
CM1
L300P inverter
Input circuits
5
4
3
2
1
L300P inverter
Input circuits
5
4
3
2
1
L300P inverter
Input circuits
5
4
3
2
1
L300P inverter
Input circuits
5
4
3
2
1

Advertisement