Second
Acceleration and
Deceleration
Functions
frequency
2CH
input
"A" Function
Func.
Name
Code
A092 Acceleration (2) time
setting
A292 Acceleration (2) time
setting, 2nd motor
A093 Deceleration (2) time
setting
A293 Deceleration (2) time
setting, 2nd motor
A094 Select method to switch
to Acc2/Dec2 profile
A294 Select method to switch
to Acc2/Dec2 profile,
2nd motor
A095 Acc1 to Acc2 frequency
transition point
A295 Acc1 to Acc2 frequency
transition point, 2nd
motor
The L300P inverter features two-stage acceleration and deceleration ramps. This gives flexibil-
ity in the profile shape. You can specify the frequency transition point, the point at which the
standard acceleration (F002) or deceleration (F003) changes to the second acceleration (A092)
or deceleration (A093). These profile options are also available for the second motor settings
and third motor settings. All acceleration and deceleration times are time to ramp from zero
speed to full speed or full speed to zero speed. Select a transition method via A094 as depicted
below. Be careful not to confuse the second acceleration/deceleration settings with settings for
the second motor!
A094=00
Accel 2
Accel 1
1
0
Description
Duration of 2nd segment of
acceleration, range is:
0.01 to 3600 sec.
Duration of 2nd segment of
acceleration, 2nd motor,
range is: 0.01 to 3600 sec.
Duration of 2nd segment of
deceleration, range is:
0.01 to 3600 sec.
Duration of 2nd segment of
deceleration, 2nd motor,
range is: 0.01 to 3600 sec.
Two options for switching
from 1st to 2nd accel/decel:
00 2CH input from terminal
01 transition frequency
Two options for switching
from1st to 2nd accel/decel:
00 2CH input from terminal
01 transition frequency (2nd
motor)
Output frequency at which
Accel1 switches to Accel2,
range is 0.00 to 400.0 Hz
Output frequency at which
Accel1 switches to Accel2,
range is 0.00 to 400.0 Hz
(2nd motor)
frequency
A094=01
t
A095
Accel 1
0
Defaults
Run
Mode
Edit
–FE2
–FU2
–FR
Lo Hi
(EU)
(US)
(JP)
✔ ✔
15.0
15.0
15.0
✔ ✔
15.0
15.0
15.0
✔ ✔
15.0
15.0
15.0
✔ ✔
15.0
15.0
15.0
✘ ✘
00
00
00
✘ ✘
00
00
00
✘ ✘
0.0
0.0
0.0
✘ ✘
0.0
0.0
0.0
3–23
L300P Inverter
Accel 2
Frequency
transition point
t
SRW Display
Units
sec.
>A092 ACCEL
TIME2
0015.00s
sec.
>A292 2ACCEL
TIME2
0015.00s
sec.
>A093 DECEL
TIME2
0015.00s
sec.
>A293 2DECEL
TIME2
0015.00s
>A094 ACCEL
CHANGE
TM
>A294 ACCEL
CHANGE
TM
Hz
>A095 ACCEL
CHFr
0000.00Hz
Hz
>A295 2ACCEL
CHFr
0000.00Hz