L100 Inverter L100 Inverter Specifications Model-specific tables for 200V and 400V class inverters The following tables are specific to L100 inverters for the 200V and 400V class model groups. Note that “General Specifications” on page 1–9 apply to both voltage class groups.
Page 2
The protection method conforms to JEM 1030. Note 2: The applicable motor refers to Hitachi standard 3-phase motor (4-pole). When using other motors, care must be taken to prevent the rated motor current (50/ 60 Hz) from exceeding the rated output current of the inverter.
Page 3
L100 Inverter L100 Inverter Specifications, continued... Item 200V Class Specifications, continued L100 inverters, CE version 015NFE 022NFE — — — 200V models UL version 015NFU 022NFU 037LFU 055LFU 075LFU Applicable motor size *2 Rated capacity (240V) kVA *10 12.7 Rated input voltage 1-phase: 200 to 240V +5%/–10%, 50/60 Hz ±5%, 3-phase: 200 to 240V +5%/–10%, 50/60 Hz ±5%, (037LFU, 055LFU &...
Page 4
L100 Inverter Specifications Item 400V Class Specifications L100 inverters, CE version 004HFE 007HFE 015HFE 022HFE 400V models UL version 004HFU 007HFU 015HFU 022HFU Applicable motor size *2 0.75 Rated capacity (460V) kVA *10 Rated input voltage 3-phase: 380 to 460V ±10%, 50/60 Hz ±5% Rated input current (A) Rated output voltage *3 3-phase: 380 to 460V (corresponding to input voltage)
L100 Inverter Item 400V Class Specifications, continued L100 inverters, CE version 030HFE 040HFE 055HFE 075HFE 400V models UL version — 040HFU 055HFU 075HFU Applicable motor size *2 Rated capacity (460V) kVA *10 10.4 12.7 Rated input voltage 3-phase: 380 to 460V ±10%, 50/60 Hz ±5% Rated input current (A) 10.0 11.0...
Page 6
L100 Inverter Specifications Item General Specifications Input Freq. Operator panel Up and Down keys / Value settings signal setting Potentiometer Analog setting External signal 0 to 10 VDC (input impedance 10k Ohms), 4 to 20 mA (input impedance 250 Ohms), Potentiometer (1k to 2k Ohms, 2W) FWD/ Operator panel Run/Stop (Forward/Reverse run change by command) External signal Forward run/stop, Reverse run/stop...
L100 Inverter Derating Curves The maximum available inverter current output is limited by the carrier frequency and ambient temperature. The carrier frequency is the inverter’s internal power switching frequency, settable from 0.5 kHz to 16 kHz. Choosing a higher carrier frequency tends to decrease audible noise, but it also increases the internal heating of the inverter, thus decreasing (derating) the maximum current output capability.
Page 8
L100 Inverter Specifications Derating curves, continued... L100–007NFE/NFU 100% % of rated output current Carrier frequency L100–0015NFE/NFU 100% % of rated output current Carrier frequency L100–022NFE/NFU 100% % of rated output current Carrier frequency...
Page 9
L100 Inverter Derating curves, continued... L100–037LF/LFU 100% % of rated output current Carrier frequency L100–055LFU 100% % of rated output current Carrier frequency L100–075LFU 100% % of rated output current Carrier frequency...
Page 10
L100 Inverter Specifications Derating curves, continued... L100–004HFE/HFU 100% % of rated output current Carrier frequency L100–007HFE/HFU 100% % of rated output current Carrier frequency L100–015HFE/HFU 100% % of rated output current Carrier frequency...
Page 11
L100 Inverter Derating curves, continued... L100–022HFE/HFU 100% % of rated output current Carrier frequency L100–040HFE/HFU 100% % of rated output current Carrier frequency L100–055HFE/HFU 100% % of rated output current Carrier frequency...
Page 12
L100 Inverter Specifications Derating curves, continued... L100–075HFE/HFU 100% % of rated output current Carrier frequency...