Command – 0A; Command – 0B - Hitachi L300P Series Instruction Manual

Three-phase input 200v class; three-phase input 400v class;
Hide thumbs Also See for L300P Series:
Table of Contents

Advertisement

B–16
Communications Protocol
Command – 0A
Command – 0B
The 0A command sets a value in the EEPROM.
The frame format of command 0A follows the
diagram and specification table.
Element
Description
STX
Control code (STart of TeXt)
Node
Node (station) address of inverter
Command
Transmission command
BCC
Block check sum code
[CR]
Control code (carriage return)
The 0B command recalculates the inverter's internal motor constants. Use this function after
the base frequency or any Hxxx parameters are changed via the serial link commands.
The frame format of command 0B follows the
diagram and specification table.
Element
Description
STX
Control code (STart of TeXt)
Node
Node (station) address of inverter
Command
Transmission command
BCC
Block check sum code
[CR]
Control code (carriage return)
Frame format
STX Node
Command
Size
Value
1 byte
STX (0x02)
2 bytes 01 to 32, and FF (broadcast to all
nodes)
2 bytes 0A
2 bytes Exclusive OR of Node,
Command, and Data
1 byte
[CR] (0x0D)
Frame format
STX Node
Command
Size
Value
1 byte
STX (0x02)
2 bytes 01 to 32
2 bytes 0B
2 bytes Exclusive OR of Node,
Command, and Data
1 byte
[CR] (0x0D)
BCC [CR]
BCC [CR]

Advertisement

Table of Contents
loading

Table of Contents