4–34
Using Intelligent Input Terminals
Run Enable for
FW/RV (–xFU2
models only)
The Run Enable for FW/RV input provides a way to enable or disable the [FW] and [RV] input
terminals in real time, including a Run command from an operator keypad. This is useful for
applications that require a logic type safety interlock for FWD Run or REV Run commands.
The Run Enable for FW/RV function is assigned to an intelligent input terminal using option
code 49. When assigned, the output frequency operates as a logical AND of the Run Enable for
FW/RV input and a [FW], [RV], or keypad Run command input. The Run Enable for RV input
is level-sensitive, as shown in the timing diagram below. The leading edges (OFF-to-ON transi-
tions) of the Run Enable for RV input and the [FW] or [RV] input can occur in any order. The
output frequency follows the logical AND of these inputs.
[ROK] terminal
[F/R] terminal
Output
frequency
Opt.
Symbol
Function Name
Code
49
ROK
Run Enable for
FW/RV
C001, C002, C003, C004,
Valid for inputs:
C005
(none)
Required
settings:
Notes:
• This function is only available on –xFU2
models.
• When the Run Enable for FW/RV function is
not assigned to any intelligent input terminal,
the FWD Run and REV Run commands
operate normally (directly control the output
frequency).
• To ensure safe inverter operation in
networked applications, you cannot change an
intelligent terminal assignment to/from
[ROK] (option code 49) via the network.
However, you can still read an [ROK] input
assignment over the network.
Input
Description
State
ON
[FW] and [RV] inputs and operator Run
key press operate normally
OFF
[FW] and [RV] inputs and operator Run
key press are ignored; inverter output
remains OFF
Example: (Requires input configuration—
see page 3–43. Jumper position shown is
for –xFU/-xFR models; for –xFE models,
see page 4–11.)
TH
FW
5
P24
PLC
CM1
See I/O specs on page 4–8.
t
ROK
4
3
2
1