Pid Loop Operation - Hitachi L300P Series Instruction Manual

Three-phase input 200v class; three-phase input 400v class;
Hide thumbs Also See for L300P Series:
Table of Contents

Advertisement

4–58

PID Loop Operation

PID Loop Operation
Standard
Multi-speed
settings
A020 to A035
Potentiometer
on keypad
V/I input
[AT]
Voltage
O
A GND
L
OI
Current
In standard operation, the inverter uses a reference source selected by parameter A001 for the
output frequency, which may be a fixed value (F001), a variable set by the front panel potenti-
ometer, or value from an analog input (voltage or current). To enable PID operation, set A071 =
01. This causes the inverter to calculate the target frequency, or setpoint. An optional intelligent
input assignment (code 23), PID Disable, will temporarily disable PID operation when active.
A calculated target frequency can have a lot of advantages. It lets the inverter adjust the motor
speed to optimize some other process variable of interest, potentially saving energy as well.
Refer to the figure below. The motor acts upon the external process. To control that external
process, the inverter must monitor the process variable. This requires wiring a sensor to either
the analog input terminal [O] (voltage) or terminal [OI] (current).
Setpoint
Error
SP
PV
Analog input
When enabled, the PID loop calculates the ideal output frequency to minimize the loop error.
This means we no longer command the inverter to run at a particular frequency, but we specify
the ideal value for the process variable. That ideal value is called the setpoint, and is specified
in the units of the external process variable. For a pump application it may be gallons/minute,
or it could be air velocity or temperature for an HVAC unit. Parameter A075 is a scale factor
that relates the external process variable units to motor frequency. The figure below is a more
detailed diagram of the PID function.
Setpoint
(Target)
setting
Scale factor
F001
reciprocal
1/A075
select
Process Variable
Analog input scaling
A076
PID V/I
input select
Inverter
Freq.
PID
Inverter
Calculation
Output
Frequency
source select
A001
Error
SP
PV
(Feedback)
A012
A011
A015
A013 A014
External
Motor
Process
Process Variable (PV)
Scale factor
A075
PID Enable
PID Disable
A071
C023
optional
intelligent input
P gain
A072
I gain
A073
D gain
A074
Scale factor
A075
Sensor
F001
Normal
PID
Frequency
setting
Monitor
D004