Maintenance And Inspection; Monthly And Yearly Inspection Chart - Hitachi L300P Series Instruction Manual

Three-phase input 200v class; three-phase input 400v class;
Hide thumbs Also See for L300P Series:
Table of Contents

Advertisement

6–10

Maintenance and Inspection

Maintenance and Inspection
Monthly and
Yearly Inspection
Chart
Item Inspected
Overall
Main
circuit
Control
circuit
Display LEDs
Check for...
Ambient
Extreme
environment
temperatures
& humidity
Major devices
Abnormal
vibration,
noise
Power supply
Voltage toler-
voltage
ance
Ground
Adequate
Insulation
resistance
Mounting
No loose
screws
Components
Overheating
Housing
Dirt, dust
Terminal block
Secure
connections
Smoothing
Leaking,
capacitor
swelling
Relay(s)
Chattering
Resistors
Cracks or
discoloring
Cooling fan
Noise
Dust
Overall
No odor,
discoloring,
corrosion
Capacitor
No leaks or
deformation
Legibility
Note 1: The life of a capacitor is affected by the ambient temperature. See
Curve" on page
Note 2: The inverter must be cleaned periodically. If dust accumulates on the fan and heat
sink, it can cause overheating of the inverter.
Inspection
Cycle
Inspection Method
Month
Year
Thermometer,
hygrometer
Visual and aural
Digital volt meter,
measure between
inverter terminals
[L1], [L2], [L3]
Megger test
Torque wrench
Thermal trip events
Visual
Visual
Visual
Aural
Visual
Power down,
manually rotate
Visual
Visual
Visual
Visual
6–12.
Criteria
Ambient temperature
between -10 to 50°C,
non-condensing
Stable environment for
electronic controls
200V class:
200 to 240V 50/60 Hz
400V class:
380 to 460V 50/60 Hz
500VDC, reading of 5M
ohms or greater, see next
section for test details
M3: 0.5 – 0.6 Nm
M4: 0.98 – 1.3 Nm
M5: 1.5 – 2.0 Nm
No trip events
Vacuum dust and dirt
No abnormalities
No abnormalities
Single click when
switching ON or OFF
Use Ohm meter to check
braking resistors
Rotation must be smooth
Vacuum to clean
No abnormalities
Undistorted appearance
All LED segments work
"Capacitor Life