Chapter 2
Installation Steps
To mount a PDU vertically, follow these steps:
1. Locate the PDU on the side of the rack opposite the cable guide(s).
Avoid the door latch near the center of the rack. The receptacles of the
PDU should face inward, not rearward. (If they face rearward, the
PDU receptacles will be blocked by the rack side panels when the rack
is fully assembled.) The power cord input (and the two "reset" buttons)
will be on the lower end of the PDU when it is in the correct position.
Use the row of holes on the
outside edge of the vertical
column.
19-Inch PDU Vertical Mounting
Detail
NOTE
With the new HP Rack System/E you may use threaded inserts
on the outside face of the rear columns to mount PDUs.
2. Use the row of mounting holes nearest the outside edge of the vertical
column. Use the hex nut and screw supplied with the PDU. Hold the
nut behind the column and insert the screw through the top mounting
Connecting and Routing Cables to the HP NetServer LPr
Figure 2-6. Mounting the PDU Vertically
Insert screw
through mounting
bracket on end of
PDU. Secure with
hex nut and lock
washer. Tighten
screw until lock
washer breaks
paint to make earth
ground.
25