Site Preparation: Circuit Breakers

When you connect the HP NetServer LPr to an AC power source, the server
temporarily draws a large "inrush current." This occurs even when the system is
in standby mode. Inrush current is much greater than the server's normal
operating needs. Generally, your external AC power source can handle the inrush
current.
If you install several HP NetServers on one circuit, however, precautions are
necessary. If there is a power failure and power is then restored, for instance, all
the servers immediately begin to draw inrush current at the same time. If the
circuit breakers on the incoming power line have insufficient capability, they may
trip and thus prevent the servers from powering up. See Appendix A,
"Specifications," for power requirements.
When preparing your site for installation, allow for the additional inrush current.
Consider the following before installing the server in your environment:
In North America, a 20-amp-minimum circuit is to be used with one
NEMA AB1 class 14B breaker for each 16-amp Power Distribution Unit
that is to be connected to an HP NetServer LPr.
In Europe:
For a single LPr unit in a rack, use a 16-amp-minimum circuit with
one IEC MCB C-type breaker for each 16-amp Power Distribution
Unit.