CARLO GAVAZZI G3800 X015 - CONFIGURATION SOFTWARE User Manual page 38

Configuration software
Table of Contents

Advertisement

G 3800 X015 Configuration Software
G 3800 X015 Configuration Software
G 3800 X015 Configuration Software
Application Example
Task:
Solution:
Object
In-/outputs
Alarm switch
Push button input
Push button input
Push button input
Semiconductor output LED for source in-
Relay output
Configuration of Master Generator
ISA alarm:
Passive detector
ISA alarm:
Acknowledgement
ISA alarm: Reset
ISA alarm: Lamp test
ISA alarm: Alarm siren Alarm sounding
38
In a chemical factory, eight laboratories are to be provided with alarm switches. Upon activation
of an alarm button, the fire staff of the factory is informed via a siren. When the fire staff has
acknowledged the alarm, they go to the lab where the alarm was started.
The alarm switches are coded for channels A1 to A8. The source of the alarm is indicated on a
panel whose LED is activated via a mimic display. The addresses correspond to those of the
alarm contacts. The fire staff uses a button coded for address B1 to acknowledge the alarms.
The alarm is reset through a reset button coded for address B2. The alarm is sounded by
means of a horn activated through a relay output of DSM 8 coded for address B4.
Function
Alarm contact
Acknowledgement
Reset
Lamp test
cation on a panel
Alarm siren
Alarm sources
Alarm
acknowledgement
Alarm reset
Activation of all
LEDs on the panel
Channel
A1..A8
B1
B2
B3
A1..A8
B4
A1.. A8
B1
B2
B3
B4
© 2002 Carlo Gavazzi Industri A/S. All rights reserved