TEMPORARY OPERATIONS
Evacuating Refrigerant Charge
Main Menu\Manual Control
1 . Navigate to
Evac/ChrgMode
.
Evac/ChrgMode
2 . If
is not available on the unit controller,
manually set all components to the states defined in
ChrgMode" on page
20 .
3 . Reclaim Refrigerant .
Charging the System with Refrigerant
Main Menu\Manual Control
1 . Navigate to
Evac/ChrgMode
.
Evac/ChrgMode
2 . If
is not available on the unit controller,
manually set all components to the states defined in
ChrgMode" on page
20 .
3 . Charge unit to value listed on the unit data plate .
WARNING
Never charge the unit with a refrigerant type other than what is listed on
the data plate. Charging with an unauthorized refrigerant type could lead to
property damage, serious personal injury, or death.
WARNING
Never perform maintenance to the refrigeration system unless refrigerant
charge has been completely evacuated, as property damage, serious
personal injury, or death may occur.
OM 1373-1
and place unit into
"Evac/
and place unit into
"Evac/
21
WWW.DAIKINAPPLIED.COM