OTHER CONFIgURATIONS
BMS Communications
Refer to the installation manuals below for detailed instructions for each BMS communication type .
• IM 916 MicroTech Unit Controller – BACnet IP
• IM 917 MicroTech Unit Controller – BACnet MSTP
• IM 918 MicroTech Unit Controller – LON Communications
LON Set-Up
Table 47: Main Menu \ BMS Communications \ LON Set-Up
Menu Display
Default
Name
Neuron ID
-
Snd Hrt Bt
60s
Rcv Hrt Bt
0s
Min Snd Tm
0s
Comm Status
-
LON BSP
-
Lon App Ver
-
OM 1373-1
Range
-
0-6553s
0-6553s
0-6553s
OK(0)
Hardware(1)
Init(2)
Memory(3)
ID(4)
COVReg(5)
Other (6)
-
-
Description
Neuron ID is a status only item that indicates the Neuron ID
of the LonWorks communication module. The Neuron ID field
displays zeros and does not populate until the communication
module has been commissioned .
Send Heartbeat .
Receive Heartbeat. Defines the maximum time that elapses after
the last update to a specified network variable input before the
unit starts to use default values . nclRCvHrBt can also be used to
change these values .
Minimum Send Time . Controls the minimum period of time
that expires before certain network variables are transmitted .
nclMinSendTime can also be used to change these values .
Comm Status shows the status of the communications .
Board Support Package. Displays the version of firmware loaded
in the LonWorks communication module .
LonWorks application version . Displays the version of the chiller
software application loaded in the LonWorks communication
module . This parameter remains blank until the communication
module is commissioned .
109