MICROTECH INPUTS/OUTPUTS
Expansion Module H I/O (POL965)
Table 75: Expansion Module H I/O (Return/Outdoor Panel)
Universal Inputs/Outputs
#
DI
AI
DO
X1
X
X2
X
X3
X
X4
X5
X6
X7
X8
X
Digital Input – 115V-230V
#
DI1
Digital Outputs – Relay (SPST, Normally Open, 230 VAC 3 Amp)
#
DO1
DO2
DO3
DO4
Digital Outputs – Solid State Relays, 24-230 VAC, 0 .5 A
#
DO5
DO6
Expansion Model I I/O (POL965)
Table 76: Expansion Module I I/O (Return/Outdoor Panel)
Universal Inputs/Outputs
#
DI
AI
DO
X1
X
X2
X
X3
X3
X4
X
X 5
X
X 6
X
X 7
X 8
X
X9
X10
X11
X12
OM 1373-1
AO
Point
OAFlow Input
Filter Switch Input 1 (Main Filter Section)
Return Air Temperature
X
DX Bypass Damper
X
OA Damper
X
Not Used
RA Humidity Sensor
Point
OADPosSw (Open/Closed)
Point
Positive Rel Damper Closure
Econo Operation Signal
Not Used
Not Used
Point
Not Used
Not Used
AO
Point
Supply Air Temp Leaving Wheel (ER_LWT)
Exhaust Air Temp Exiting Wheel (ER_EWT)
X
Relief Dampers
X
Energy Recovery Wheel Command
Exhaust Air Plenum Static Pressure
Filter Transducer 1 (Main Filter Section)
Filter Transducer 2 (Main Filter Section)
X
Energy Recovery SCR Preheat
RFEF Flow Input
NA
NA
NA
NA
Comments
0-10VDC or 4-20 mA
Dry Contacts
10K Thermistor Coefs/ InputType = 7
0-10 VDC
0-10 VDC
4-20 mA
Comments
Comments
Comments
Comments
10K Thermistor Coefs/ InputType = 7
10K Thermistor Coefs/ InputType = 7
0-10 VDC
0-10VDC
4-20mA
4-20mA
4-20mA
1-10VDC
4-20 mA
151