A2L DETECTION AND MITIgATION
GID
Name
id
56
Sensor 6 Level
57
Sensor 6 State
58
Sensor 6 Faults
59
Sensor 6
Temperature
60
Sensor 6
Humidity
61
Sensor 6
Pressure
62
Sensor 7
Address
63
Sensor 7 Level
64
Sensor 7 State
65
Sensor 7 Faults
66
Sensor 7
Temperature
67
Sensor 7
Humidity
68
Sensor 7
Pressure
69
Sensor 8
Address
70
Sensor 8 Level
71
Sensor 8 State
72
Sensor 8 Faults
73
Sensor 8
Temperature
74
Sensor 8
Humidity
75
Sensor 8
Pressure
76
DF Saving Time
77
Nominated
Sensor Addr
78
Sensor Reset
Command
79
Sen Func Reset
Result
DAIKIN APPLIED
Min
Max
Default
Limit
Limit
0
65535
0
1
65535
0
0
65535
0
-400
940
0
0
1000
0
0
4000
0
0
GID14
GID14
+ 7
0
65535
0
1
65535
0
0
65535
0
-400
940
0
0
1000
0
0
4000
0
0
GID14
GID14
+ 7
0
65535
0
1
65535
0
0
65535
0
-400
940
0
0
1000
0
0
4000
0
15
120
15
48
55
55
0
1
0
0
1
0
Description
Sensor 6 LFL reported value . For instance value = 200, then LFL
is 20% .
Sensor 6 current state . Value = 2, then state is "run" .
Sensor 6 internal faults reported . For instance value = 0, then no
faults .
Sensor 6 Temperature reported value . For instance value = 250,
then Temp = 25 C .
Sensor 6 Humidity reported value . For instance value = 400, then
Humidity = 40% .
Sensor 6 Pressure reported value . Not available for now .
Sensor 7 Address .
Sensor 7 LFL reported value . For instance value = 200, then LFL
is 20% .
Sensor 7 current state . Value = 2, then state is "run" .
Sensor 7 internal faults reported . For instance value = 0, then no
faults .
Sensor 7 Temperature reported value . For instance value = 250,
then Temp = 25 C .
Sensor 7 Humidity reported value . For instance value = 400, then
Humidity = 40% .
Sensor 7 Pressure reported value . Not available for now .
Sensor 8 Address .
Sensor 8 LFL reported value . For instance value = 200, then LFL
is 20% .
Sensor 8 current state . Value = 2, then state is "run" .
Sensor 8 internal faults reported . For instance value = 0, then no
faults .
Sensor 8 Temperature reported value . For instance value = 250,
then Temp = 25 C .
Sensor 8 Humidity reported value . For instance value = 400, then
Humidity = 40% .
Sensor 8 Pressure reported value . Not available for now .
Data Flash saving time in minutes . How frequent data is saved on
non volatile memory .
Sensor address to be reset to the default value .
Command to invoke sensor function reset, value = 1 then this
command is invoked .
Final result of the sensor reset function operation . Value = 0, the
operation was successful .
196
MICROTECH UNIT CONTROLLER

Advertisement

loading
Need help?

Need help?

Do you have a question about the MICROTECH 4 and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Mt3106
Save PDF