9.4
Removal
10
Maintenance
Installation and operating instructions • Wilo-Control EC-WP • Ed.01/2024-08
2.
Turn the operating button until menu 3.00 appears
3.
Press the operating button.
Menu 3.01 appears.
4.
Press the operating button.
5.
Change value to "off".
6.
Press the operating button.
Value saved, pump switched off.
7.
Turn main switch to the "OFF" position.
8.
Secure the main switch against being activated by unauthorised persons (e.g. lock
main switch)
Switchgear switched off.
DANGER
Danger of death due to electrical current!
Improper conduct when carrying out electrical work can lead to death
due to electric shock!
• Before all electrical work, disconnect the product from the mains and
secure it against being switched on again without authorisation.
• Electrical work must be carried out by a qualified electrician!
• Observe local regulations!
Decommissioning performed.
Mains connection is switched so that it is voltage-free and safeguarded against being
activated by unauthorised persons.
The power connection for fault and run signals is switched so that it is voltage-free
and safeguarded against being activated by unauthorised persons.
1.
Open the switchgear.
2.
Disconnect all connection cables and pull them out through the threaded cable con-
nection.
3.
Close off the ends of the connection cables watertight.
4.
Seal threaded cable connections watertight.
5.
Support the switchgear (e.g. get a second person to help).
6.
Loosen the switchgear fastening screws and remove the switchgear from the struc-
ture.
Switchgear removed. Observe the following for storage!
DANGER
Danger of death due to electrical current!
Improper conduct when carrying out electrical work can lead to death
due to electric shock!
• Before all electrical work, disconnect the product from the mains and
secure it against being switched on again without authorisation.
• Electrical work must be carried out by a qualified electrician!
• Observe local regulations!
NOTICE
Unauthorised work or structural changes are prohibited!
Only maintenance and repair work described in this manual may be car-
ried out. All other works and any alterations to the construction may only
be carried out by the manufacturer.