8.5
During operation
Installation and operating instructions • Wilo-Control EC-WP • Ed.01/2024-08
✓
Direction of rotation correct.
✓
Motor current monitoring set correctly.
1.
Start Easy Actions menu: Turn control knob 180°.
2.
Select the pump for automatic mode: Turn the control knob until the menu item is dis-
played:
– Pump 1: P1 Auto
– Pump 2: P2 Auto
3.
Press the control knob.
⇒
Automatic mode is set for the selected pump. Alternatively, setting can be per-
formed in menu 3.02 to 3.03.
▶
Automatic mode switched on.
Automatic mode after shutdown
✓
The switchgear is closed.
✓
Checked configuration.
✓
Parameter input enabled: Menu 7.01 shows on.
1.
Press the control knob for 3 s.
⇒
Menu 1.00 appears.
2.
Turn the control knob until menu 3.00 appears
3.
Press the control knob.
⇒
Menu 3.01 appears.
4.
Press the control knob.
5.
Change value to "on".
6.
Press the control knob.
⇒
Value saved, pump enabled.
▶
Automatic mode switched on.
Make sure the following points are observed during operation:
•
Keep the switchgear closed and secure it against unauthorised opening.
•
Switchgear attached in an overflow-proof manner (protection class IP54).
•
Not exposed to direct sunlight.
•
Ambient temperature: 0 ... 40 °C.
The following items of information are shown on the main screen:
•
Pump status:
–
Number of registered pumps
–
Pump activated/deactivated
–
Pump On/Off
•
Operation with standby pump
•
Control mode
•
Actual pressure value or float switch status
•
Active fieldbus operation
Furthermore, the following information is available via Menu 4:
1.
Press the control knob for 3 s.
⇒
Menu 1.00 appears.
2.
Turn the control knob until Menu 4 appears.
3.
Press the control knob.
en
53