Fig. 89: Menu 1.10
Fig. 90: Menu 1.11
Installation and operating instructions • Wilo-Control EC-WP • Ed.01/2024-08
Menu no.
1.10
Name
Peak-load pump activation delay
Value range
1 – 30 s
Factory setting
3 s
Description
Delay for starting a peak-load pump when the start threshold
has been reached and the current value remains permanently
above the activation threshold.
Menu no.
1.11
Name
Peak-load pump switch-off delay
Value range
0 ... 30 s
Factory setting
1 s
Description
Delays the stop of a peak-load pump when the stop threshold
has been reached and the actual value remains permanently
above the deactivation threshold.