6.6.15
"Constant pressure control p-c"
control mode: 1x pump, with pres-
sure switch
p
2
Fig. 47: Functional diagram
1
6
Fig. 48: Screen display
Function
Terminal overview symbol
Float switch operating principle
Top contact
Bottom contact
Pressure switch operating principle
Contact closed
Contact open
Menu and value to be set
34
1
Activation point
2
Deactivation point
NOTICE! If a pressure switch is used, only one pump can be controlled. The pressure switch
used detects the actual pressure value and defines the activation and deactivation threshold:
•
If the pressure in the system falls below the activation threshold, the pump switches on.
•
If the deactivation threshold is exceeded, the pump switches off after the set switch-off
1
delay has elapsed.
To protect the pump from a dry run, install an additional float switch or electrode in the well:
•
If the water level falls below the dry running level, the pump switches off. An error mes-
Q
sage appears on the display and an alarm sounds.
•
If the dry-running level is exceeded, the alarm and error message are automatically reset.
1
Current pump status
3
Control mode
4
Switching state of pressure switch
3
6
Fieldbus active
4
Overview of terminals
DR
-
25 26
27 28
1/(2)
closed
−
open
−
−
−
−
−
Required menu settings
ON/OFF
-
29 30
31 32
off
on/(off)
1
2
1/(2)
−
−
−
−
Pump off
−
Pump on
−
Installation and operating instructions • Wilo-Control EC-WP • Ed.01/2024-08
-
-
-
33 34
35 36
45 46
4-20 mA
In
off
on/(off)
2
2
−
−
−
−
−
−
−
−
−
−
−
−
-
49 50
2
-
-
−
−
Need help?