46
Menu no.
5.62
Name
Delay dry-running protection
Value range
0 – 180 s
Factory setting
0 s
Description
The delay for detecting dry run to avoid false alarms caused by
short impulses.
Menu no.
5.63
Name
Delay restart after dry run
Value range
0 – 1800 s
Factory setting
10 s
Description
Time until the pumps start again after the end of the dry run-
ning signal.
Menu no.
5.66
Name
Acoustic alarm
Value range
off, error
Factory setting
off
Description
Enables the activation of an acoustic signal when an alarm oc-
curs.
•
•
Menu no.
5.67
Name
Output for an external signalling unit On/Off
Value range
off, error
Factory setting
off
Description
Enables the activation of an optical signal when an alarm oc-
curs.
•
•
Menu no.
5.68
Name
Rotating field detection
Value range
on, off
Factory setting
on
Description
Activation or deactivation of the phase rotating field detection
when single-phase pumps are used.
•
•
Menu no.
5.69
Name
Minimum current detection pumps
Value range
on, off
Factory setting
on
Description
Activate or deactivate undercurrent detection for the pumps:
If the motor current is below the set minimum, the minimum
current detection reports an error.
•
•
Installation and operating instructions • Wilo-Control EC-WP • Ed.01/2024-08
off = alarm off
error = alarm on
off = output deactivated
error = output activated
off = rotating field detection deactivated
on = rotating field detection activated
off = minimum current detection deactivated
on = minimum current detection activated