Field settings table
Breadcrumb
Setting name
9.3.4
[6-03]
Capacity step 1
9.3.5
[6-04]
Additional capacity step 2
9.3.6
[5-00]
Equilibrium: Deactivate backup heater (or external backup heat
source in case of a bivalent system) above the equilibrium
temperature for space heating?
9.3.7
[5-01]
Equilibrium temperature
9.3.8
[4-00]
Operation
└─ Booster heater
9.4.1
[6-02]
Capacity
9.4.3
[8-03]
BSH eco timer
9.4.4
[4-03]
Operation
└─ Emergency
9.5.1
[4-06]
Emergency
9.5.2
[7-06]
HP forced OFF
└─ Balancing
9.6.1
[5-02]
Space heating priority
9.6.2
[5-03]
Priority temperature
9.6.3
[5-04]
Offset BSH setpoint
9.6.4
[8-02]
Anti-recycle timer
9.6.5
[8-00]
Minimum running timer
9.6.6
[8-01]
Maximum running timer
9.6.7
[8-04]
Additional timer
Installer settings
9.7
[4-04]
Water pipe freeze prevention
└─ Benefit kWh power supply
9.8.2
[D-00]
Allow heater
9.8.3
[D-05]
Allow pump
(*1) *X*_(*2) *H*_(*3) *B*_(*4) *EKECBUA*3V_
(*5) *EKECBUA*6V_(*6) *EKECBUA*9W_(*7) BUH less_
(*8) 300L tank_(*9) E_(*10) E7
Range, step
Default value
R/W
0~10kW, step: 0,2kW
0kW
2kW (*5)
3kW (*4, *6, *7)
R/W (*5,
0~10kW, step: 0,2kW
*6)
0kW (*4)
R/O (*4,
3kW (*7)
*7)
4kW (*5)
6kW (*6)
R/W
0: No (*10)
1: Yes (*9)
R/W
-15~35°C, step: 1°C
0°C
R/W
0: Restricted
1: Allowed
2: Only DHW
R/W
0~10kW, step: 0,2kW
0kW
R/W
20~95 min, step: 5 min
50 min
R/W
0: Restricted
1: Allowed
2: Overlap
3: Compressor off
4: Legionella only
R/W
0: Manual
1: Automatic
2: Auto SH reduced/ DHW ON
3: Auto SH reduced/ DHW OFF
4: Auto SH normal/ DHW OFF
R/W
0: Disabled
1: Enabled
R/W
0: Disabled
1: Enabled
R/W
-15~35°C, step: 1°C
0°C
R/W
0~20°C, step: 1°C
10°C
R/W
0~10 hour, step: 0,5 hour
0,5 hour
R/O
0~20 min, step 1 min
1 min
R/W
5~95 min, step: 5 min
30 min
R/W
0~95 min, step: 5 min
95 min
R/W
0: Continuous pump operation
1: Non continuous pump operation
2: OFF
R/W
0: No
1: Only BSH
2: Only BUH
3: All
R/W
0: No
1: Yes
9/19
4P681797-1C - 2023.07