Symptom: You are feeling too cold (hot) in your living room..................57 Symptom: The water at the tap is too cold........................57 Symptom: Heat pump failure ............................57 Symptom: The system is making gurgling noises after commissioning................. 58 User reference guide ETSH/X(B)16P30+50EF Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Page 3
Overview: Relocation ..............................60 10 Disposal 11 Glossary 12 Installer settings: Tables to be filled in by installer 12.1 Configuration wizard............................... 63 12.2 Settings menu ................................. 64 ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Format: Paper (in the box of the indoor unit) + Digital files on http:// www.daikineurope.com/support-and-manuals/product-information/ Latest revisions of the supplied documentation may be available on the regional Daikin website or via your installer. The original documentation is written in English. All other languages are translations. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O...
About this document Daikin Residential Controller app If set up by your installer, you can use the Daikin Residential Controller app to control and monitor the status of your system. For more information, see: http://www.onlinecontroller.daikineurope.com/ Breadcrumbs Breadcrumbs (example: [4.3]) help you to locate where you are in the menu structure of the user interface.
Page 6
Example: " 1–3 Figure title" means "Figure 3 in chapter 1". Indicates a table title or a reference to it. Example: " 1–3 Table title" means "Table 3 in chapter 1". ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Do NOT place any objects containing water on the unit. CAUTION ▪ Do NOT place any objects or equipment on top of the unit. ▪ Do NOT sit, climb or stand on the unit. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Do NOT use cleaning materials or means to accelerate the defrosting process other than those recommended by the manufacturer. ▪ Be aware that the refrigerant inside the system is odourless. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Page 9
Reason: Refrigerant might leak into the water circuit, and subsequently into the room when you purge air from the heat emitters or collectors. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
User interface of the indoor unit e Dedicated Human Comfort Interface (BRC1HHDA used as room thermostat) f Underfloor heating g Radiators, heat pump convectors, or fan coil units ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Operation > Space heating/cooling), room frost protection operation –if enabled– can still activate. However, for leaving water temperature control and external room thermostat control, the protection is NOT guaranteed. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Page 12
You can use the leaving water temperature setpoint screen to read out and adjust the desired leaving water temperature. 1 Go to [2]: Main zone or [3]: Additional zone. Main zone Additional zone ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Page 13
X2. X1, X2 Outdoor ambient temperature Y1~Y4 Desired leaving water temperature a WD curve before changes b WD curve after changes c Slope d Offset ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Tank), disinfection mode will remain active. However, if you turn it OFF while disinfection is running, an AH error occurs. 1 Go to [C.3]: Operation > Tank. Operation Space heating/cooling Tank ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Page 15
In other modes, you can only view the setpoint screen but not modify it. More information For more information, see also: ▪ "5.4 Turning operation ON or OFF" [ 24] ▪ "5.7 Domestic hot water control" [ 31] ▪ "5.8 Preset values and schedules" [ 34] ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Slot for WLAN cartridge With the WLAN cartridge, the installer can connect the system to the internet. As user you can then control the system via the Daikin Residential Controller app. Note: This slot cannot be used for SD cards.
Page 17
: Turn the right dial. Navigate through the possible values and settings. ▪ : Press the right dial. Confirm your choice and go to the next menu item. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
(**) Only accessible by installer (***) Only applicable when WLAN is installed INFORMATION Depending on the selected installer settings and unit type, settings will be visible/ invisible. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
26 Feb 2019 22:19 Possible actions on this screen Go through the list of the main menu. Go to the main menu screen. Enable/disable breadcrumbs. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Page 20
Quiet mode active Outdoor unit Indoor unit / domestic hot water tank Floor-standing indoor unit with integrated tank Wall-mounted indoor unit Wall-mounted indoor unit with separated tank Water pressure ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Page 21
"8.1 To display the help text in case of a malfunction" [ 56] for more information. If the corresponding operation (for example: space heating) is not active, the circle is greyed out. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
User settings mode and quiet mode. Displays data and information about the Information indoor unit. Installer settings Restriction: Only for the installer. Gives access to advanced settings. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Adjust and automatically apply the desired temperature. Item Description Minimum temperature limit Fixed by the unit Restricted by the installer Maximum temperature limit Fixed by the unit Restricted by the installer ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Space heating/cooling operation a Space heating/cooling operation ON b Space heating/cooling operation OFF ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Disinfection mode. Even if you turn OFF tank heating operation ([C.3]: Operation > Tank), disinfection mode will remain active. However, if you turn it OFF while disinfection is running, an AH error occurs. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
5.6 Space heating/cooling control 5.6.1 About space heating/cooling control Controlling space heating/cooling typically consists of the following stages: Setting the space operation mode Controlling the temperature ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Restricted per month according to the Operation mode schedule [4.2]. To restrict automatic changeover according to a schedule Conditions: You set the space operation mode to Automatic. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Main zone Additional zone (if any) Room thermostat control External room thermostat control External room thermostat control No icon Leaving water Leaving water temperature control temperature control ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Only adjust the leaving water temperature settings in case of problems. You can use the leaving water temperature setpoint screen to read out and adjust the desired leaving water temperature. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Page 30
[2.1]: Main zone > Schedule ▪ [3.1]: Additional zone > Schedule 2 Select No. To enable weather-dependent operation for the leaving water temperature "5.9.4 Using weather-dependent curves" [ 46]. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
In reheat mode the storage tank continuously heats up to the temperature shown on the home screen (example: 50°C) when the temperature drops below a certain value. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
▪ When the tank temperature drops below a preset value (=set temperature – hysteresis value; example 50°C), the tank is heated up to 60°C. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
You cannot wait for the next scheduled action to heat up the domestic hot water tank. Then you can activate powerful operation. The domestic hot water tank will start heating up the water to the tank temperature setpoint. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
"Activation screen" in "Possible to a schedule. schedules" [ 35] Select which schedule you currently want to use for a specific control. The system contains some predefined schedules. You can: ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Page 35
This entry shows you where to activate it. ▪ Possible actions: Actions you can use when programming a schedule. For most schedules, you can program up to 6 actions per day. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Page 36
"To set the space operation mode" [ 27]. cooling > Operation mode schedule Schedule (per month) for when to operate the unit in heating mode and when in cooling mode. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
1 Go to the schedule. 2 (optional) Clear the content of the whole week schedule or the content of a selected day schedule. 3 Program the schedule for Monday. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Page 38
Friday User defined 1 2 Select Delete. Delete Edit Copy 3 Select OK to confirm. To program the schedule for Monday 1 Select Monday. User defined 1 ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Page 39
1 Select Monday. User defined 1 2 Select Copy. Delete Edit Copy Result: Next to the copied day, "C" is displayed. 3 Select Tuesday. User defined 1 ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Page 40
8:00 21°C 23:00 18°C --:-- 4 Confirm the changes. 5 Select Saturday. 6 Select Copy. 7 Select Sunday. 8 Select Paste. Result: User defined 1 ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Electricity: 12 euro cents/kWh [7.5.1]=12 To set the gas price 1 Go to [7.6]: User settings > Gas price. 2 Select the correct gas price. 3 Confirm the changes. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Page 42
To set the electricity price in case of an incentive per kWh renewable energy Calculate the value for the electricity price with following formula: ▪ Actual electricity price+Incentive/kWh ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
See "5.9.4 Using weather-dependent curves" [ 46]. 5.9.2 2-points curve Define the weather-dependent curve with these two setpoints: ▪ Setpoint (X1, Y2) ▪ Setpoint (X2, Y1) Example ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Examples Weather-dependent curve when slope is selected: Weather-dependent curve when offset is selected: ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
5.9.4 Using weather-dependent curves Configure weather-dependent curves as following: To define the setpoint mode To use the weather-dependent curve, you need to define the correct setpoint mode: ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Page 47
You cannot configure the curve with temperatures that are higher or lower than the set maximum and minimum setpoints for that zone or for the tank. When the maximum or minimum setpoint is reached, the curve flattens out. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
↓ ↑ ↓ ↓ ↓ ↓ ↓ "5.9.2 2-points curve" [ 44]. 5.10 Other functionalities 5.10.1 To configure time and date 1 Go to [7.2] User settings > Time/date. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Setting the starting date and ending date of your holiday. Activating the holiday mode. To check if holiday mode is activated and/or running is displayed on the home screen, holiday mode is active. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Restriction: WLAN settings are only visible when a WLAN module is installed. About the WLAN module The wireless LAN module connects the heat pump system to the internet. As user you can then control the heat pump system via the Daikin Residential Controller app. This needs the following components:...
Page 51
See: http://www.onlinecontroller.daikineurope.com/ Configuration To configure the Daikin Residential Controller app, follow the in-app instructions. While doing this, the following actions and information are needed on the user interface of the indoor unit: [D] Wireless gateway...
Page 52
The Daikin Residential Controller app needs to be installed on the user's smartphone. See: http://www.onlinecontroller.daikineurope.com/ Configuration To configure the Daikin Residential Controller app, follow the in-app instructions. While doing this, the following actions and information are needed on the user interface: [D] Wireless gateway...
Page 53
[D.6] Cloud connection: Read out the status of the connection to the cloud: 1 Go to [D.6]: Wireless gateway > Cloud connection. 2 Read out the connection status: ▪ Not connected ▪ Connected ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Make sure the desired DHW temperature, reflected by storage tank temperature, is NOT too high. Example: After installation, lower the tank temperature daily by 1°C and check if you still have enough hot water. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
▪ Do NOT use the unit until a service person confirms that the part from which the refrigerant leaked has been repaired. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Conditions: The user permission level is set to advanced end user. 1 Go to [8.2]: Information > Malfunction history. You see a list of the most recent malfunctions. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
When the heat pump fails to operate, the backup heater or boiler can serve as an emergency heater. It then takes over the heat load either automatically or by manual interaction. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
We recommend to purge air with the air purge function of the unit (to be performed by the installer). If you purge air from the heat emitters or collectors, mind the following: ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Page 59
If yes, make sure that the room where you want to purge air is sufficiently ventilated. Reason: Refrigerant might leak into the water circuit, and subsequently into the room when you purge air from the heat emitters or collectors. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
If you want to relocate parts of your system, contact your installer. You can find the contact/helpdesk number via the user interface. 1 Go to [8.3]: Information > Dealer information. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Do NOT try to dismantle the system yourself: dismantling of the system, treatment of the refrigerant, oil and other parts MUST comply with applicable legislation. Units MUST be treated at a specialised treatment facility for reuse, recycling and recovery. ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Optional equipment Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation. Field supply Equipment NOT made by Daikin that can be combined with the product according to the instructions in the accompanying documentation.
Additional zone (only if [4.4]=1, dual zone) Emitter type [3.7] Control (read only) [3.9] Setpoint mode [3.4] Schedule [3.1] WD curve type [3.C] (read only) Tank Heat up mode [5.6] Hysteresis [5.9] ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Installer settings: Tables to be filled in by installer 12.2 Settings menu Setting Fill in… Main zone Thermostat type [2.A] Additional zone (if applicable) Thermostat type [3.A] Information Dealer information [8.3] ETSH/X(B)16P30+50EF User reference guide Daikin Altherma 3 H HT ECH₂O 4P679470-1 – 2022.02...
Page 68
4P679470-1 0000000V 4P679470-1 2022.02 Verantwortung für Energie und Umwelt...