Objects
7.1.3.16. RoomTemperature_status (Analog Input Object Type)
It reports the ambient temperature perceived by the sensor from the AC system side.
NOTE
To know more, see
Property Identifier
Property Datatype
Object_Identifier
BACnetObjectIdentifier
Object_Name
CharacterString
Object_Type
BACnetObjectType
Present_Value
REAL
Description
CharacterString
Device_Type
CharacterString
Status_Flags
BACnetStatusFlags
Event_State
BACnetEventState
Reliability
BACnetReliability
Out_Of_Service
BOOLEAN
Update_Interval
Unsigned
Units
BACnetEngineeringUnits
Min_Pres_Value
REAL
Max_Pres_Value
REAL
Resolution
REAL
COV_Increment
REAL
Time_Delay
Unsigned
Notification_Class
Unsigned
High_Limit
REAL
Low_Limit
REAL
Deadband
REAL
Limit_Enable
BACnetLimitEnable
Event_Enable
BACnetEventTransitionBits
Acked_Transitions
BACnetEventTransitionBits
Notify_Type
BACnetNotifyType
Event_Time_Stamps
BACnetArray[N] of BACnetTimeStamp
Profile_Name
CharacterString
NOTE
You can set the temperature scale in Celsius or Fahrenheit scale via DIP switches. More information
in
DIP switches (page
USER MANUAL Version 1.0.9
Considerations on Temperature Signals (page
Value
(Analog Input, 1)
RoomTemperature_status
ANALOG_INPUT (0)
10 .. 38°C / 50 .. 100°F
-
-
{FALSE, FALSE/TRUE, FALSE, FALSE}
STATE_NORMAL (0)
NO_FAULT_DETECTED (0), UNRELIABLE_OTHER (7)
FALSE
-
Celsius degrees (62)
Fahrenheit degrees (64)
10°C / 50°F
38°C / 100°F
-
0
-
-
-
-
-
-
-
-
-
-
-
9).
IN485FGL001I000 Gateway
67).
ASHRAE
R
R
R
R
O
O
R
R
O
R
O
R
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
Gateway
R
R
R
R
-
-
R
R
R
R
-
R
-
-
-
W
-
-
-
-
-
-
-
-
-
-
-