Onoff_Status (Binary Input Object Type) - HMS Networks Intesis IN485FGL001I000 User Manual

Fujitsu residential and vrf systems to bacnet ms/tp and modbus rtu
Hide thumbs Also See for Intesis IN485FGL001I000:
Table of Contents

Advertisement

Objects

7.1.3.2. OnOff_status (Binary Input Object Type)

It indicates if the indoor unit is turned on or off.
Property Identifier
Property Datatype
Object_Identifier
BACnetObjectIdentifier
Object_Name
CharacterString
Object_Type
BACnetObjectType
Present_Value
BACnetBinaryPV
Description
CharacterString
Device_Type
CharacterString
Status_Flags
BACnetStatusFlags
Event_State
BACnetEventState
Reliability
BACnetReliability
Out_Of_Service
BOOLEAN
Polarity
BACnetPolarity
Inactive_Text
CharacterString
Active_Text
CharacterString
Change_Of_State_Time
BACnetDatetime
Change_Of_State_Count
Unsigned
Time_Of_State_Count_Reset
BACnetDatetime
Elapsed_Active_Time
Unsigned
Time_Of_Active_Time_Reset
BACnetDatetime
Time_Delay
Unsigned
Notification_Class
Unsigned
Alarm_Value
BACnetBinaryPV
Event_Enable
BACnetEventTransitionBits
Acked_Transitions
BACnetEventTransitionBits
Notify_Type
BACnetNotifyType
Event_Time_Stamps
BACnetArray[N] of BACnetTimeStamp
Profile_Name
CharacterString
USER MANUAL Version 1.0.9
Value
(Binary Input, 0)
OnOff_status
BINARY_INPUT (3)
INACTIVE (0) / ACTIVE (1)
-
-
{FALSE, FALSE/TRUE, FALSE, FALSE}
STATE_NORMAL (0)
NO_FAULT_DETECTED (0), UNRELIABLE_OTHER
(7)
FALSE
NORMAL (0)
Off
On
-
-
-
-
-
-
-
-
-
-
-
-
-
IN485FGL001I000 Gateway
ASHRAE
Gateway
R
R
R
R
R
R
R
R
O
-
O
-
R
R
R
R
O
R
R
R
R
R
O
R
O
R
O
-
O
-
O
-
O
-
O
-
O
-
O
-
O
-
O
-
O
-
O
-
O
-
O
-
Page 19 of 74

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Intesis IN485FGL001I000 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Table of Contents