HMS Networks Intesis IN485MHI001R000 User Manual

HMS Networks Intesis IN485MHI001R000 User Manual

Mitsubishi heavy industries residential and vrf systems to bacnet ms/tp
Hide thumbs Also See for Intesis IN485MHI001R000:
Table of Contents

Advertisement

Quick Links

ENGLISH
IN485MHI001R000 GATEWAY
                                         Mitsubishi Heavy Industries Residential
and VRF Systems to BACnet MS/TP
USER MANUAL
Version 1.0.5
Publication date 2024-07-29

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Intesis IN485MHI001R000 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for HMS Networks Intesis IN485MHI001R000

  • Page 1 ENGLISH IN485MHI001R000 GATEWAY                                          Mitsubishi Heavy Industries Residential and VRF Systems to BACnet MS/TP USER MANUAL Version 1.0.5 Publication date 2024-07-29...
  • Page 2 The information in this document shall therefore not be construed as a commitment on the part of HMS Networks and is subject to change without notice. HMS Networks makes no commitment to update or keep current the information in this document.
  • Page 3: Table Of Contents

    IN485MHI001R000 Gateway Table of Contents 1. Description, Compatible AC systems, and Order Codes ..............1 2. General Information ........................ 2 2.1. Intended Use of the User Manual ..................2 2.2. General Safety Information ....................2 2.3. Admonition Messages and Symbols ..................3 3.
  • Page 4 IN485MHI001R000 Gateway 7.3.21. FilterSign (Binary Input Object Type) ................39 7.3.22. FilterReset (Binary Output Object Type) ..............40 7.3.23. Occupancy (Multistate Value Object Type) ..............41 7.3.24. OccupiedCoolSetPoint (Analog Value Object Type) ............42 7.3.25. OccupiedHeatSetPoint (Analog Value Object Type) ............43 7.3.26.
  • Page 5: Description, Compatible Ac Systems, And Order Codes

    Description, Compatible AC systems, and Order Codes IN485MHI001R000 Gateway 1. Description, Compatible AC systems, and Order Codes BACnet MS/TP gateway for Mitsubishi Heavy Industries air conditioners. Compatible with residential and VRF air conditioning systems commercialized by Mitsubishi Heavy Industries. Use the compatibility tool to get a complete list of compatible units: https://compatibility.intesis.com/# ORDER CODE LEGACY ORDER CODE...
  • Page 6: General Information

    IN485MHI001R000 Gateway General Information 2. General Information 2.1. Intended Use of the User Manual This manual contains the main features of this Intesis gateway and the instructions for its appropriate installation, configuration, and operation. The contents of this manual should be brought to the attention of any person who installs, configures, or operates this gateway or any associated equipment.
  • Page 7: Admonition Messages And Symbols

    Admonition Messages and Symbols IN485MHI001R000 Gateway 2.3. Admonition Messages and Symbols DANGER Instructions that must be followed to avoid an imminently hazardous situation that, if not avoided, will result in death or severe injury. WARNING Instructions that must be followed to avoid a potentially hazardous situation that, if not avoided, could result in death or severe injury.
  • Page 8: Quickstart Guide For The In485Mhi001R000 Gateway

    IN485MHI001R000 Gateway Quickstart Guide for the IN485MHI001R000 Gateway 3. Quickstart Guide for the IN485MHI001R000 Gateway IMPORTANT Disconnect all systems from power before connecting them to the gateway. Mount the gateway in the desired installation site. This gateway can be mounted over a DIN rail, a wall, or inside the indoor unit (in some indoor unit models only).
  • Page 9: Overview

    This document assumes that the user is familiar with BACnet and Mitsubishi Heavy Industries technologies and their technical terms. 4.1. Inside the Package Items included: • Intesis IN485MHI001R000 gateway • Installation guide 4.2. Main Features • BTL mark ensures full interoperability with BACnet devices.
  • Page 10: Gateway Capacity

    This Intesis gateway can integrate one single Mitsubishi Heavy Industries AC unit and its associated elements. 4.4. General Functionality With this Intesis IN485MHI001R000 gateway, you can easily integrate Mitsubishi Heavy Industries residential and VRF air conditioning systems into a system based on BACnet MS/TP. To do so, the gateway acts as a server device of the installation itself, accessing all signals from the AC indoor unit.
  • Page 11: Hardware

    Hardware IN485MHI001R000 Gateway 5. Hardware 5.1. Mounting Mount the gateway inside the AC indoor unit, over a wall, or over a DIN rail. IMPORTANT Do not mount the gateway in air-handling units or conducts. NOTE DIN rail mounting inside a grounded metallic cabinet is recommended. Mounting the gateway inside the AC indoor unit Look for the proper place to mount the gateway, taking into consideration the following: IMPORTANT...
  • Page 12: Connection Procedure

    IN485MHI001R000 Gateway Connection Procedure NOTE For some DIN rails, to complete step 2, you may need a small screwdriver or similar to pull the bottom clip down. 5.2. Connection Procedure CAUTION Disconnect all systems from power before connecting them to the gateway. IMPORTANT Keep communication cables away from power and ground wires.
  • Page 13: Coexistence Of The Gateway With A Remote Controller

    Coexistence of the Gateway with a Remote Controller IN485MHI001R000 Gateway Connection to the wired remote controller (RC) bus NOTE Mount the gateway in the desired place before wiring it. Connect the gateway at any point of the XY bus. NOTE •...
  • Page 14: Connection To An External Power Supply

    IN485MHI001R000 Gateway Connection to an External Power Supply NOTE Although it is not mandatory, we recommend connecting a wired RC in the bus since it may be necessary to establish proper communication between the gateway and some indoor units. IMPORTANT The roles of the gateway and the wired RC affect certain functions, such as using a temperature sensor from the BMS side or the Virtual Temperature function.
  • Page 15: Dip Switches

    DIP switches IN485MHI001R000 Gateway 5.5. DIP switches The gateway includes three DIP switches: SW1 (8 switches) at the bottom and SW2 (8 switches) and SW3 (3 switches) at the top. IMPORTANT The DIP switches configuration will only take effect after rebooting the gateway. Table 1.
  • Page 16 IN485MHI001R000 Gateway DIP switches Table 2. SW2 (P1 to P7): BACnet MS/TP MAC address; (P8): Temperature unit (°C/°F) Binary value Switches MAC address Description b0 .. b7 0 0 0 0 0 0 0 X 1 0 0 0 0 0 0 X 0 1 0 0 0 0 0 X 1 1 0 0 0 0 0 X 1 0 1 1 1 1 1 X...
  • Page 17: Led Indicators

    LED Indicators IN485MHI001R000 Gateway 5.6. LED Indicators There are two LEDs at the lower side of the gateway, between the DIP switch block SW1 and the Power connector. When powering the gateway up, both LEDs blink once and then turn off. After that, LEDs will behave as described in the table below: Table 4.
  • Page 18: Technical Specifications

    IN485MHI001R000 Gateway Technical Specifications 5.7. Technical Specifications Plastic, type PC (UL 94 V-0) Housing Net dimensions (HxWxD): 93 x 53 x 58 mm / 3.7 x 2.1 x 2.3” Color: Light grey. RAL 7035 Weight 85 g (3 oz) Wire cross-section/gauge per terminal: One core: 0.2 ..
  • Page 19: Restore The Factory Settings

    Restore the Factory Settings IN485MHI001R000 Gateway 6. Restore the Factory Settings To restore the gateway to its factory settings, proceed as follows: Set all switches from DIP switches SW1 and SW2 to the ON position. Reboot the gateway: Power it OFF. Power it ON.
  • Page 20: Objects

    IN485MHI001R000 Gateway Objects 7. Objects 7.1. Supported Object Types Object type Analog-Input Analog-Output Analog-Value Binary-Input Binary-Output Binary-Value Device Multistate-Input Multistate-Output Multistate-Value 7.2. Member Objects 7.2.1. Type: Gateway Object name Description Object type Object instance IN485MHI001R000 Mitsubishi Heavy Industries RC gateway 8: Device 246000 (default) 7.2.2.
  • Page 21 Member Objects IN485MHI001R000 Gateway Object name Object type Object instance Occupancy OccupiedCoolSetpoint OccupiedHeatSetpoint UnoccupiedCoolSetpoint UnoccupiedHeatSetpoint OccupancyContinuousCheck UnoccupiedDeadBandAction LockRemoteControl OutdoorTemp_status CenterRemote DIP_SW_S1_status DIP_SW_S2_status SerialNumber USER MANUAL Version 1.0.5 Page 17 of 63...
  • Page 22: Objects And Properties

    IN485MHI001R000 Gateway Objects and Properties 7.3. Objects and Properties 7.3.1. Mitsubishi Heavy Industries AC Gateway (Device Object Type) Object_Identifier: The gateway can be identified in the BACnet network either manually or automatically: • Automatic address (default): The gateway address is generated by combining the base address + the local address configured in the DIP switch block SW2 (P1 to P7).
  • Page 23 Objects and Properties IN485MHI001R000 Gateway Property Identifier Property Datatype Value ASHRAE Intesis Local_Date Date Local_Time Time UTC_Offset INTEGER Daylight_Savings_Status BOOLEAN APDU_Segment_Timeout Unsigned 3000 APDU_Timeout Unsigned 3000 Number_of_APDU_ Retries Unsigned List_Of_Session_Keys List of BACnetSessionKey Time_Synchronization_ Recipients List of BACnetRecipient Max_Master Unsigned Max_Info_Frames Unsigned Device_Address_Binding...
  • Page 24: Onoff_Status (Binary Input Object Type)

    IN485MHI001R000 Gateway Objects and Properties 7.3.2. OnOff_status (Binary Input Object Type) It indicates if the indoor unit is turned on or off. Property Identifier Property Datatype Value ASHRAE Gateway Object_Identifier BACnetObjectIdentifier (Binary Input, 0) Object_Name CharacterString OnOff_status Object_Type BACnetObjectType BINARY_INPUT (3) Present_Value BACnetBinaryPV INACTIVE (0) / ACTIVE (1)
  • Page 25: Onoff_Command (Binary Output Object Type)

    Objects and Properties IN485MHI001R000 Gateway 7.3.3. OnOff_command (Binary Output Object Type) It turns the indoor unit on or off. Property Identifier Property Datatype Value ASHRAE Gateway Object_Identifier BACnetObjectIdentifier (Binary Output, 0) Object_Name CharacterString OnOff_command Object_Type BACnetObjectType BINARY_OUTPUT (4) Present_Value BACnetBinaryPV INACTIVE (0) / ACTIVE (1) Description CharacterString...
  • Page 26: Mode_Status (Multistate Input Object Type)

    IN485MHI001R000 Gateway Objects and Properties 7.3.4. Mode_status (Multistate Input Object Type) It indicates the indoor unit's current mode. Property Identifier Property Datatype Value ASHRAE Gateway Object_Identifier BACnetObjectIdentifier (Multistate Input, 0) Object_Name CharacterString Mode_status Object_Type BACnetObjectType MULTISTATE_INPUT (13) Present_Value Unsigned 1 .. 5 Description CharacterString Device_Type...
  • Page 27: Mode_Command (Multistate Output Object Type)

    Objects and Properties IN485MHI001R000 Gateway 7.3.5. Mode_command (Multistate Output Object Type) It sets the AC indoor unit's mode. Property Identifier Property Datatype Value ASHRAE Gateway Object_Identifier BACnetObjectIdentifier (Multistate Output,0) Object_Name CharacterString Mode_command Object_Type BACnetObjectType MULTISTATE_OUTPUT (14) Present_Value Unsigned 1 .. 5 Description CharacterString Device_Type...
  • Page 28: Setpoint_Status (Analog Input Object Type)

    IN485MHI001R000 Gateway Objects and Properties 7.3.6. Setpoint_status (Analog Input Object Type) It reports the temperature setpoint requested to the indoor unit. NOTE To know more, see Considerations on Temperature Signals (page 60). Property Identifier Property Datatype Value ASHRAE Gateway Object_Identifier BACnetObjectIdentifier (Analog Input, 0) Object_Name...
  • Page 29: Setpoint_Command (Analog Output Object Type)

    Objects and Properties IN485MHI001R000 Gateway 7.3.7. Setpoint_command (Analog Output Object Type) It is used to request a temperature setpoint from the BACnet side. NOTE To know more, see Considerations on Temperature Signals (page 60). Property Identifier Property Datatype Value ASHRAE Gateway Object_Identifier BACnetObjectIdentifier...
  • Page 30: Virtualtemperatureactive (Binary Input Object Type)

    IN485MHI001R000 Gateway Objects and Properties 7.3.8. VirtualTemperatureActive (Binary Input Object Type) It indicates if the Virtual Temperature function is active or inactive. NOTE The Virtual Temperature function allows the gateway to set the reference temperature using the value reported by a sensor connected to the BMS. For more information, see Ambient Temperature and Virtual Temperature Function (page 56).
  • Page 31: Fanspeed_Status (Multistate Input Object Type)

    Objects and Properties IN485MHI001R000 Gateway 7.3.9. FanSpeed_status (Multistate Input Object Type) It indicates the indoor unit's fan speed. Property Identifier Property Datatype Value ASHRAE Gateway Object_Identifier BACnetObjectIdentifier (Multistate Input, 1) Object_Name CharacterString FanSpeed_status Object_Type BACnetObjectType MULTISTATE_INPUT (13) Present_Value Unsigned 1 .. 5 Description CharacterString Device_Type...
  • Page 32: Fanspeed_Command (Multistate Output Object Type)

    IN485MHI001R000 Gateway Objects and Properties 7.3.10. FanSpeed_command (Multistate Output Object Type) It sets the indoor unit's fan speed. Property Identifier Property Datatype Value ASHRAE Gateway Object_Identifier BACnetObjectIdentifier (Multistate Output, 1) Object_Name CharacterString FanSpeed_command Object_Type BACnetObjectType MULTISTATE_OUTPUT (14) Present_Value Unsigned 1 .. 5 Description CharacterString Device_Type...
  • Page 33: Airdirectionud_Status (Multistate Input Object Type)

    Objects and Properties IN485MHI001R000 Gateway 7.3.11. AirDirectionUD_status (Multistate Input Object Type) It indicates the indoor unit's vertical air direction (up-down) status. Property Identifier Property Datatype Value ASHRAE Gateway Object_Identifier BACnetObjectIdentifier (Multistate Input, 2) Object_Name CharacterString AirDirectionUD_status Object_Type BACnetObjectType MULTISTATE_INPUT(13) Present_Value Unsigned 1 ..
  • Page 34: Airdirectionud_Command (Multistate Output Object Type)

    IN485MHI001R000 Gateway Objects and Properties 7.3.12. AirDirectionUD_command (Multistate Output Object Type) It sets the indoor unit's vertical air direction (up-down). Property Identifier Property Datatype Value ASHRAE Gateway Object_Identifier BACnetObjectIdentifier (Multistate Output, 2) Object_Name CharacterString AirDirectionUD_command Object_Type BACnetObjectType MULTISTATE_OUTPUT (14) Present_Value Unsigned 1 ..
  • Page 35: Roomtemperature_Status (Analog Input Object Type)

    Objects and Properties IN485MHI001R000 Gateway 7.3.13. RoomTemperature_status (Analog Input Object Type) It reports the ambient temperature perceived by the sensor from the AC system side. It can be reported by the indoor unit or the wired remote controller's sensor. NOTE To know more, see Ambient Temperature and Virtual Temperature Function (page 56).
  • Page 36: Roomtemperature_Command (Analog Output Object Type)

    IN485MHI001R000 Gateway Objects and Properties 7.3.14. RoomTemperature_command (Analog Output Object Type) It is used to write the ambient temperature perceived by a sensor from the BACnet side. NOTE To know more, see Considerations on Temperature Signals (page 60). Property Identifier Property Datatype Value ASHRAE...
  • Page 37: Errorcode (Analog Input Object Type)

    Objects and Properties IN485MHI001R000 Gateway 7.3.15. ErrorCode (Analog Input Object Type) It indicates the AC system's current error. Property Identifier Property Datatype Value ASHRAE Gateway Object_Identifier BACnetObjectIdentifier (Analog Input, 2) Object_Name CharacterString ErrorCode Object_Type BACnetObjectType ANALOG_INPUT (0) Present_Value REAL 0 .. 90, 65535 Description CharacterString Device_Type...
  • Page 38: Errorcodem (Multistate Input Object Type)

    IN485MHI001R000 Gateway Objects and Properties 7.3.16. ErrorCodeM (Multistate Input Object Type) It indicates the AC system's current error. Property Identifier Property Datatype Value ASHRAE Gateway Object_Identifier BACnetObjectIdentifier (Multistate Input, 4) Object_Name CharacterString ErrorCodeM Object_Type BACnetObjectType MULTISTATE_INPUT(13) Present_Value Unsigned 0 .. 90, 65535 Description CharacterString Device_Type...
  • Page 39: Erroractive (Binary Input Object Type)

    Objects and Properties IN485MHI001R000 Gateway 7.3.17. ErrorActive (Binary Input Object Type) It indicates if there is an active error in the AC system. Property Identifier Property Datatype Value ASHRAE Gateway Object_Identifier BACnetObjectIdentifier (Binary Input, 1) Object_Name CharacterString ErrorActive Object_Type BACnetObjectType BINARY_INPUT (3) Present_Value BACnetBinaryPV...
  • Page 40: Erroraddress (Analog Input Object Type)

    IN485MHI001R000 Gateway Objects and Properties 7.3.18. ErrorAddress (Analog Input Object Type) It indicates the address of the indoor unit which is reporting the error. Property Identifier Property Datatype Value ASHRAE Intesis Object_Identifier BACnetObjectIdentifier (Analog Input, 4) Object_Name CharacterString ErrorAddress Object_Type BACnetObjectType ANALOG_INPUT (0) Present_Value...
  • Page 41: Errorreset (Binary Output Object Type)

    Objects and Properties IN485MHI001R000 Gateway 7.3.19. ErrorReset (Binary Output Object Type) It resets the error signal. Property Identifier Property Datatype Value ASHRAE Intesis Object_Identifier BACnetObjectIdentifier (Binary Output, 5) Object_Name CharacterString ErrorReset Object_Type BACnetObjectType BINARY_OUTPUT (4) Present_Value BACnetBinaryPV INACTIVE (0) / ACTIVE (1) Description CharacterString Device_Type...
  • Page 42: Ontimecounter (Analog Value Object Type)

    IN485MHI001R000 Gateway Objects and Properties 7.3.20. OnTimeCounter (Analog Value Object Type) It indicates the AC unit running time. Property Identifier Property Datatype Value ASHRAE Gateway Object_Identifier BACnetObjectIdentifier (Analog Value, 0) Object_Name CharacterString OnTimeCounter Object_Type BACnetObjectType ANALOG_VALUE (2) Present_Value REAL 0 .. 65535 Description CharacterString Status_Flags...
  • Page 43: Filtersign (Binary Input Object Type)

    Objects and Properties IN485MHI001R000 Gateway 7.3.21. FilterSign (Binary Input Object Type) It indicates the status of the filter. Property Identifier Property Datatype Value ASHRAE Intesis Object_Identifier BACnetObjectIdentifier (Binary Input, 1) Object_Name CharacterString FilterSign Object_Type BACnetObjectType BINARY_OUTPUT (4) Present_Value BACnetBinaryPV INACTIVE (0) / ACTIVE (1) Description CharacterString Device_Type...
  • Page 44: Filterreset (Binary Output Object Type)

    IN485MHI001R000 Gateway Objects and Properties 7.3.22. FilterReset (Binary Output Object Type) It resets the filter signal. Property Identifier Property Datatype Value ASHRAE Intesis Object_Identifier BACnetObjectIdentifier (Binary Output, 4) Object_Name CharacterString FilterReset Object_Type BACnetObjectType BINARY_OUTPUT (4) Present_Value BACnetBinaryPV INACTIVE (0) / ACTIVE (1) Description CharacterString Device_Type...
  • Page 45: Occupancy (Multistate Value Object Type)

    Objects and Properties IN485MHI001R000 Gateway 7.3.23. Occupancy (Multistate Value Object Type) It indicates the current occupancy status. NOTE To know more, see Occupancy Function (page 54). Property Identifier Property Datatype Value ASHRAE Gateway Object_Identifier BACnetObjectIdentifier (Multistate Value, 0) Object_Name CharacterString Occupancy Object_Type BACnetObjectType...
  • Page 46: Occupiedcoolsetpoint (Analog Value Object Type)

    IN485MHI001R000 Gateway Objects and Properties 7.3.24. OccupiedCoolSetPoint (Analog Value Object Type) It indicates the temperature setpoint when the room is occupied, the cool mode is selected, and the occupancy object is enabled. NOTE To know more, see Occupancy Function (page 54).
  • Page 47: Occupiedheatsetpoint (Analog Value Object Type)

    Objects and Properties IN485MHI001R000 Gateway 7.3.25. OccupiedHeatSetPoint (Analog Value Object Type) It indicates the temperature setpoint when the room is occupied, the heat mode is selected, and the occupancy object is enabled. NOTE To know more, see Occupancy Function (page 54).
  • Page 48: Unoccupiedcoolsetpoint (Analog Value Object Type)

    IN485MHI001R000 Gateway Objects and Properties 7.3.26. UnoccupiedCoolSetPoint (Analog Value Object Type) It indicates the setpoint when the room is unoccupied, the cool mode is selected, and the occupancy object is enabled. NOTE To know more, see Occupancy Function (page 54). Property Identifier Property Datatype Value...
  • Page 49: Unoccupiedheatsetpoint (Analog Value Object Type)

    Objects and Properties IN485MHI001R000 Gateway 7.3.27. UnoccupiedHeatSetPoint (Analog Value Object Type) It indicates the setpoint temperature when the room is unoccupied, the heat mode is selected, and the occupancy object is enabled. NOTE To know more, see Occupancy Function (page 54).
  • Page 50: Occupancycontinuouscheck (Binary Value Object Type)

    IN485MHI001R000 Gateway Objects and Properties 7.3.28. OccupancyContinuousCheck (Binary Value Object Type) It indicates if the system is continuously checking the setpoint and occupancy conditions. NOTE To know more, see Occupancy Function (page 54). Property Identifier Property Datatype Value ASHRAE Gateway Object_Identifier BACnetObjectIdentifier (Binary Value, 0)
  • Page 51: Unoccupieddeadbandaction (Binary Value Object Type)

    Objects and Properties IN485MHI001R000 Gateway 7.3.29. UnoccupiedDeadbandAction (Binary Value Object Type) It indicates the action to be performed when Unoccupancy is enabled, and Room Temperature is within the deadband. NOTE To know more, see Occupancy Function (page 54). Property Identifier Property Datatype Value ASHRAE...
  • Page 52: Lockremotecontrol (Binary Value Object Type)

    IN485MHI001R000 Gateway Objects and Properties 7.3.30. LockRemoteControl (Binary Value Object Type) It is used to lock or unlock the AC remote controller. Property Identifier Property Datatype Value ASHRAE Gateway Object_Identifier BACnetObjectIdentifier (Binary Value, 2) Object_Name CharacterString LockRemoteControl Object_Type BACnetObjectType BINARY_VALUE (5) Present_Value BACnetBinaryPV INACTIVE (0) / ACTIVE (1)
  • Page 53: Outdoortemp_Status (Analog Input Object Type)

    Objects and Properties IN485MHI001R000 Gateway 7.3.31. OutdoorTemp_status (Analog Input Object Type) It indicates the outdoor temperature from the outdoor unit sensor. Property Identifier Property Datatype Value ASHRAE GATEWAY Object_Identifier BACnetObjectIdentifier (Analog Input, 8) Object_Name CharacterString OutdoorTemp_status Object_Type BACnetObjectType ANALOG_INPUT (0) Present_Value REAL -25 ..
  • Page 54: Centerremote (Multistate Input Object Type)

    IN485MHI001R000 Gateway Objects and Properties 7.3.32. CenterRemote (Multistate Input Object Type) Property Identifier Property Datatype Value ASHRAE Gateway Object_Identifier BACnetObjectIdentifier (Multi-state Input, 0) Object_Name CharacterString CenterRemote Object_Type BACnetObjectType MULTISTATE_INPUT (13) Present_Value Unsigned 1 .. 6 Description CharacterString Device_Type CharacterString Status_Flags BACnetStatusFlags {FALSE, FALSE/TRUE, FALSE, FALSE} Event_State...
  • Page 55: Dip_Sw_S1_Status (Analog Input Object Type)

    Objects and Properties IN485MHI001R000 Gateway 7.3.33. DIP_SW_S1_status (Analog Input Object Type) It indicates the status of the DIP switch block SW1 in decimal value. To get the status of each individual switch (position) of SW1, just convert it to binary. The gateway reads this value only when booting up. Property Identifier Property Datatype Value...
  • Page 56: Dip_Sw_S2_Status (Analog Input Object Type)

    IN485MHI001R000 Gateway Objects and Properties 7.3.34. DIP_SW_S2_status (Analog Input Object Type) It indicates the status of the DIP switch block SW2 in decimal value. To get the status of each individual switch (position) of SW2, just convert it to binary. The gateway reads this value only when booting up. Property Identifier Property Datatype Value...
  • Page 57: Serialnumber (Analog Input Object Type)

    Objects and Properties IN485MHI001R000 Gateway 7.3.35. SerialNumber (Analog Input Object Type) It indicates the serial number of the gateway with the pattern 000EXXXXX, where: • 000E is constant and not included in the Present Value property. • XXXXX is the unique device serial number. This is the information provided by the Present Value. Property Identifier Property Datatype Value...
  • Page 58: Occupancy Function

    IN485MHI001R000 Gateway Occupancy Function 8. Occupancy Function The Occupancy function determines the AC unit's behavior depending on the presence or absence of people in the room. This signal is processed directly in the Intesis gateway and has the capacity to modify three parameters of the AC system: Setpoint, Mode, and On/Off.
  • Page 59 Occupancy Function IN485MHI001R000 Gateway – If this object's value is 0 (inactive), the gateway only checks the occupancy when the occupancy status changes. • Unoccupied Deadband Action: It determines the AC unit's behavior when the room is unoccupied and the ambient temperature is within the deadband.
  • Page 60: Ambient Temperature And Virtual Temperature Function

    IN485MHI001R000 Gateway Ambient Temperature and Virtual Temperature Function 9. Ambient Temperature and Virtual Temperature Function The IN485MHI001R000 gateway enables the use of a temperature sensor from the BACnet-based BMS. The reason for using this sensor could be that it is better positioned than the sensor in the indoor unit or the wired remote controller.
  • Page 61 Ambient Temperature and Virtual Temperature Function IN485MHI001R000 Gateway Set the Mitsubishi Heavy Industries AC system to read the temperature provided by the sensor inside the wired RC. NOTE This configuration must be performed by a Mitsubishi Heavy Industries authorized installer through the remote controller.
  • Page 62 IN485MHI001R000 Gateway Ambient Temperature and Virtual Temperature Function The Virtual Temperature function can be activated with the gateway acting either as the header or the follower of the wired RC bus. • Procedure with the gateway acting as the header of the RC bus: Set the IN485MHI001R000 gateway as the header of the bus by setting the SW1-1 (DIP switch 1, position 1) ON.
  • Page 63 Ambient Temperature and Virtual Temperature Function IN485MHI001R000 Gateway NOTICE Due to the formula applied by the Virtual Temperature function, the temperature reported by the AC system and the actual ambient temperature may differ. This must not be taken as an error, but as the normal behavior when the Virtual Temperature function is working.
  • Page 64: Considerations On Temperature Signals

    IN485MHI001R000 Gateway Considerations on Temperature Signals 9.1. Considerations on Temperature Signals NOTE You can set the temperature signals in degrees Celsius or Fahrenheit via the DIP switch SW2. More information in DIP switches (page 11). Table 13. Objects dedicated to temperature signals and to the Virtual Temperature function BACnet object Function when the Virtual Temperature function Function when the Virtual Temperature function is...
  • Page 65 Considerations on Temperature Signals IN485MHI001R000 Gateway After a few minutes, the technician checks the BACnet object RoomTemperature_command (Analog Output) to find the temperature perceived by the BMS sensor: 19°C. Then, she looks at the BACnet object RoomTemperature_status (Analog Input), which reports the temperature sensed by the indoor unit: 24°C. At this point, the formula applied by the Virtual Temperature function is based on these numbers: 24-(19-20)=25.
  • Page 66: Error Codes

    IN485MHI001R000 Gateway Error Codes 10. Error Codes NOTE The error codes displayed in the remote controller may vary depending on the AC unit model. Read the documentation of your unit to know its specific error codes. Code in the wired Error code Description No active error...
  • Page 67 Error Codes IN485MHI001R000 Gateway Code in the wired Error code Description Outdoor unit fan motor error Low pressure error/Service valve closed Ice storage unit error Abnormal freezing, insufficient water supply/Inverter error Water temperature sensor disconnection Suction pipe temperature sensor disconnection High/Low pressure sensor anomaly Underneath temperature sensor disconnection Power transistor temperature sensor disconnection...