IN485FGL001I000 Gateway
Register Name
VIRTUAL TEMP ACTIVE
WINDOW CONTACT STEP
WINDOW CONTACT RELOAD LAST VALUE
WINDOW CONTACT LOCK WHEN OPEN
WINDOW TIMEOUT (IN MINUTES)
MACHINE MODE
MACHINE MIN SETPOINT COOL
MACHINE MAX SETPOINT COOL
MACHINE MIN SETPOINT HEAT
MACHINE MAX SETPOINT HEAT
POLL TIMEOUT (ms)
DEVICE IDENTIFIER
MODE_MAP
FAN_MAP
VANES_MAP
U_D_VANES_MAP
L_R_VANES_MAP
Page 64 of 74
Possible values
0: Not active
1: Active
0: Idle (window is closed)
1: Timeout1 (window is opened, timeout starts)
2: Timeout2 (it doesn't apply to window contact)
3: Window contact applies (window is opened, time is
finished, window contact action is applied)
0: No (default)
1: Yes
0: No
1:Yes
0 .. 30
0: Normal
1: Autochangeover
2: Limited setpoint
Value in °C; °F; x1; x10
Default value: 24°C / 75°F
NOTE
Set the temperature units via the DIP
switch SW2.
Value in °C; °F; x1; x10
Default value: 28°C / 82°F
NOTE
Set the temperature units via the DIP
switch SW2.
Value in °C; °F; x1; x10
Default value: 19°C / 66°F
NOTE
Set the temperature units via the DIP
switch SW2.
Value in °C; °F; x1; x10
Default value: 23°C / 73°F
NOTE
Set the temperature units via the DIP
switch SW2.
Time between polls (in milliseconds)
Default value: 5000 ms
12034
Indicates the available states of the signal. Each bit in the
register has its own meaning. See the table below.
Indicates the available states of the signal. Each bit in the
register has its own meaning. See the table below.
Indicates the available states of the signal. Each bit in the
register has its own meaning. See the table below.
Indicates the available states of the signal. Each bit in the
register has its own meaning. See the table below.
Indicates the available states of the signal. Each bit in the
register has its own meaning. See the table below.
Modbus Registers
Modbus
PLC
address
address
R/W
(base 0)
(base 1)
129
130
R
130
131
R
1000
1001
R/W
1001
1002
R/W
1002
1003
R/W
1150
1151
R/W
1153
1154
R/W
1154
1155
R/W
1155
1156
R/W
1156
1167
R/W
1160
1161
R/W
2000
2001
R
2001
2002
R
2002
2003
R
2003
2004
R
2004
2005
R
2005
2006
R