Advertisement

DIP switches
Table 3. Dip switch SW2 when the gateway is set for Modbus RTU: (P1 to P6): Modbus server address; (P7):
Degree decimals setting (P8): Temperature unit (°C/°F)
Binary value
b0 .. b7
1
2
3
1 0 0 0 0 0 X X
ON
OFF
OFF
0 1 0 0 0 0 X X
OFF
ON
OFF
1 1 0 0 0 0 X X
ON
ON
OFF
...
1 0 1 1 1 1 X X
ON
OFF
ON
0 1 1 1 1 1 X X
OFF
ON
ON
1 1 1 1 1 1 X X
ON
ON
ON
X X X X X X 0 X
X
X
X
X X X X X X 1 X
X
X
X
X X X X X X X 0
X
X
X
X X X X X X X 1
X
X
X
Table 4. DIP switch SW3: (P1 to P3): BACnet/Modbus polarization and termination resistor
Binary value
Position
b0 .. b2
1
2
3
0 X X
OFF
X
X
1 X X
ON
X
X
X 0 0
X
OFF
OFF
X 1 1
X
ON
ON
IMPORTANT
The DIP switches configuration will only take effect after rebooting the gateway.
USER MANUAL Version 1.0.9
Position
Modbus address
4
5
6
7
8
OFF
OFF
OFF
X
X
OFF
OFF
OFF
X
X
OFF
OFF
OFF
X
X
ON
ON
ON
X
X
ON
ON
ON
X
X
ON
ON
ON
X
X
X
X
X
OFF
X
X
X
X
ON
X
X
X
X
X
OFF
X
X
X
X
ON
EIA-485 bus without termination resistor. The gateway is not at one end of the EIA-485 bus (default value)
120 Ω termination resistor active. The gateway is at one end of the EIA-485 bus
No bus polarization (default value)
Description
1
2
3
...
61
62
63
Temperature values in Modbus register are
-
represented in degrees x1 (default)
Temperature values in Modbus register are
-
represented in degrees x10. Example: 19.2°=192
-
Temperature in Celsius (default)
-
Temperature in Fahrenheit
Description
Bus polarization active
IN485FGL001I000 Gateway
-
-
-
-
-
-
-
Page 11 of 74