Occupancy Function
– If this object's value is 0 (inactive), the gateway only checks the occupancy when the occupancy status
changes.
• Unoccupied Deadband Action: It determines the AC unit's behavior when the room is unoccupied and the
ambient temperature is within the deadband.
– If this object's value is 1 (active), the indoor unit will remain on.
– If this object's value is 0 (inactive), the indoor unit will turn off.
When there is presence in the room, and according to the current room temperature, the AC unit's mode,
setpoint, and on/off will be set to:
Condition
Room temperature > OCS
Room temperature < OHS
OCS < Room temperature > OHS
When there is no presence in the room, and according to the current room temperature, the AC unit's mode,
setpoint and on/off will be set to:
Condition
Room temperature > OCS
Room temperature < OHS
UCS/UHS depending on the current mode
OCS < Room temperature >
(If Fan or Dry mode is active, no setpoint is
OHS
NOTICE
Any local change (for example with the remote control) in the Setpoint, Mode, or the On/Off signal
will disable the Occupancy function.
USER MANUAL Version 1.0.9
Setpoint
Current OCS value
Current OCS value
OCS/OHS depending on the current mode
(If Fan or Dry mode is active, no setpoint is sent)
Setpoint
Current UCS value
Current UHS value
sent)
Mode
On/Off
Cool
On
Heat
On
Current mode
On
Mode
On/Off
Cool
On
Heat
On
On
(Deadband
action=1)
Current
mode
Off
(Deadband
action=0)
IN485FGL001I000 Gateway