4.1.3.12. RoomTemperature_status (Analog Input Object Type)

It indicates the room temperature perceived by the AC indoor unit sensor.
Property Identifier
Property Datatype
Object_Identifier
BACnetObjectIdentifier
Object_Name
CharacterString
Object_Type
BACnetObjectType
Present_Value
REAL
Description
CharacterString
Device_Type
CharacterString
Status_Flags
BACnetStatusFlags
Event_State
BACnetEventState
Reliability
BACnetReliability
Out_Of_Service
BOOLEAN
Update_Interval
Unsigned
Units
BACnetEngineeringUnits
Min_Pres_Value
REAL
Max_Pres_Value
REAL
Resolution
REAL
COV_Increment
REAL
Time_Delay
Unsigned
Notification_Class
Unsigned
High_Limit
REAL
Low_Limit
REAL
Deadband
REAL
Limit_Enable
BACnetLimitEnable
Event_Enable
BACnetEventTransitionBits
Acked_Transitions
BACnetEventTransitionBits
Notify_Type
BACnetNotifyType
Event_Time_Stamps
BACnetArray[N] of BACnetTimeStamp
Profile_Name
CharacterString
Page 22 of 65
Value
(Analog Input, 1)
RoomTemperature_status
ANALOG_INPUT (0)
-10 .. 50°C / 14 .. 122°F
-
-
{FALSE, FALSE/TRUE, FALSE, FALSE}
STATE_NORMAL (0)
NO_FAULT_DETECTED (0), UNRELIABLE_OTHER (7)
FALSE
-
Celsius degrees (62)
Fahrenheit degrees (64)
-10°C / 14°F
50°C / 122°F
-
0
-
-
-
-
-
-
-
-
-
-
-
Objects
ASHRAE
Gateway
R
R
R
R
R
R
R
R
O
-
O
-
R
R
R
R
O
R
R
R
O
-
R
R
O
-
O
-
O
-
O
W
O
-
O
-
O
-
O
-
O
-
O
-
O
-
O
-
O
-
O
-
O
-