IN485FGL001I000 Gateway

7.1.3.32. RemoteControllerProhibit_command (Multistate Output Object Type)

It allows control over the indoor unit's Remote Controller.
Property Identifier
Property Datatype
Object_Identifier
BACnetObjectIdentifier
Object_Name
CharacterString
Object_Type
BACnetObjectType
Present_Value
Unsigned
Description
CharacterString
Device_Type
CharacterString
Status_Flags
BACnetStatusFlags
Event_State
BACnetEventState
Reliability
BACnetReliability
Out_Of_Service
BOOLEAN
Number_Of_States
Unsigned
State_Text
BACnetArray[N] of CharacterString
Priority_Array
BACnetPriorityArray
Relinquish_Default
Unsigned
Time_Delay
Unsigned
Notification_Class
Unsigned
Feedback_Value
Unsigned
Event_Enable
BACnetEventTransitionBits
Acked_Transitions
BACnetEventTransitionBits
Notify_Type
BACnetNotifyType
Event_Time_Stamps
BACnetArray[N] of BACnetTimeStamp
Profile_Name
CharacterString
Table 17. RemoteControllerProhibit_Command
Present_Value
1
2
Page 50 of 74
Value
(Multistate Output,5)
RemoteControllerProhibit__command
MULTISTATE_OUTPUT (14)
1 .. 2
-
-
{FALSE, FALSE, FALSE, FALSE}
STATE_NORMAL (0)
NO_FAULT_DETECTED (0)
UNRELIABLE_OTHER (7)
FALSE
2
Check the Remote Controller Prohibit Command table
below
BACnetPriorityArray
1
-
-
-
-
-
-
-
-
State_Text
Unlocked
Locked
Objects
ASHRAE
Gateway
R
R
R
R
R
R
W
W
O
-
O
-
R
R
R
R
O
R
R
R
R
R
O
R
R
R
R
R
O
-
O
-
O
-
O
-
O
-
O
-
O
-
O
-