Changing the DC Injection Brake Current Using an Analog Input
If you set H3-09 (Multi-function Analog Input Terminal A2 Function Selection) or H3-05 (Multi-function
Analog Input Terminal A3 Function Selection) to 6 (DC injection brake current), you can change the DC
injection brake current level using the analog input.
At 10 V input (voltage) or 20 mA input (current), 100% of the Inverter rated current will be applied.

Using an Emergency Stop

Set a multi-function input terminal (H1-
eration time set in C1-09. If inputting the emergency stop with an NO contact, set the multi-function input ter-
minal (H1-
terminal (H1-
After the emergency stop command has been input, operation cannot be restarted until the Inverter has
stopped. To cancel the emergency stop, turn OFF the run command and emergency stop command.
Related parameters
Con-
stant
Number
C1-09
* The acceleration and deceleration settings range varies depending on the setting in C1-10. When C1-10 is set to 0, the acceleration/deceleration settings
range is 0.00 to 600.00 (seconds).
-14
6
DC injection brake voltage level
Inverter rated current
Fig 6.17 DC Injection Brake Current Using an Analog Input
) to 15, and if inputting the emergency stop with an NC contact, set the multi-function input
) to 17.
Name
Description
Display
Emergency
The deceleration time when the
stop time
multi-function input "Emergency
(fast) stop" is set to ON.
This function can be used a
Fast Stop Time
stopped method when a fault has
been detected.
) to 15 or 17 (emergency stop) to decelerate to a stop at the decel-
Change
Setting
Factory
during
Range
Setting
Opera-
tion
0.0 to
10.0 s
No
*
6000.0
Control Methods
Open
Open
V/f
Flux
Loop
Loop
V/f
with
Vec-
Vector
Vector
PG
tor
1
2
A
A
A
A
A