Omron VARISPEED G7 Instruction Manual page 332

Hide thumbs Also See for VARISPEED G7:
Table of Contents

Advertisement

Error Display
RDE
DATA ERROR
Select READ Permitted
Prevent overwriting the data stored in EEPROM in the Digital Operator by mistake. With o3-02 set to 0, if you
set o3-01 to 1, and perform the write operation, PrE will be displayed on the Digital Operator, and the write
operation will be stopped.
Writing Constant Set Values Stored in the Digital Operator to the Inverter (COPY)
To write constant set values stored in the Digital Operator to the Inverter, make the settings using the follow-
ing method.
Step
Digital Operator Display
No.
-ADV-
** Main Menu **
1
Programming
-ADV-
Initialization
2
A1
- 00=1
Select Language
-ADV-
COPY Function
3
o3
- 01=0
Copy Funtion Sel
-ADV-
Copy Funtion Sel
4
o3-01=
0
*0*
COPY SELECT
-ADV-
Copy Funtion Sel
5
o3-01=
2
*0*
OP→INV WRITE
-ADV-
COPY
6
OP→INV COPYING
-ADV-
COPY
7
COPY COMPLETE
-ADV-
Copy Funtion Sel
8
o3 - 01=0
*0*
COPY SELECT
Tried to write constants to EEPROM on the Digital Operator, but unable to perform write
operation.
Table 6.2 COPY Function Procedure
Press the MENU Key, and select advanced programming mode.
Press the DATA/ENTER Key, and select the constants monitor display.
Display o3-01 (Copy Function Selection) using the Increment Key and Decrement
Key.
Press the DATA/ENTER Key, and select the constants setting display.
Change the set value to 2 using the Increment Key.
Set the changed data using the DATA/ENTER Key. The COPY function will start.
If the COPY function ends normally, End is displayed on the Digital Operator.
The display returns to o3-01 when a key is pressed.
Digital Operator Functions
Meaning
Explanation
137
6-