Trial Operation Procedure

Perform trial operation according to the following flowchart.
Select operating
method.
(Default: A1-02 = 0)
Settings according
to control mode
-2
4
START
Installation
Wiring
*1
Set power supply voltage.
Turn ON power.
Confirm status.
Basic settings
(Quick programming mode)
Vector (A1-02 = 2, 3, or 4)*5
V/f control?
YES
V/f
V/f with PG
(A1-02 = 1)
PG?
Set E1-03.
V/f default: 200 V/60 Hz(400 V/60 Hz)
Motor cable over
50 m or heavy load possibly
causing motor to stall or
overload?
NO
Application settings
(Advanced programming mode)
No-load operation
Loaded operation
Optimum adjustments and
constant settings
Check/record constants.
END
Fig 4.1 Trial Operation Flowchart
Set E1-03, E2-04, and F1-01.
V/f default: 200 V/60 Hz (400 V/60 Hz)
YES
motor during autotuning?
Stationary autotuning for
*4
Rotational autotuning
line-to-line resistance only
*1 Set for 400 V Class Inverter for 55 kW or more.
*2 If there is a reduction gear between the motor and PG, set
the reduction ratio in F1-12 and F1-13 in advanced
programming mode.
*3 Use rotational autotuning to increase autotuning accuracy
whenever it is okay for the motor to be operated.
*4 If the motor cable changes to 50 m or longer for the actual
installation, perform stationary autotuning for the line-to-line
resistance only on-site.
*5 The default control mode is open-loop vector control 2
(A1-02 = 2).
*6 If the maximum output frequency and base frequency
are different, set the maximum output frequency (E1-
04) after autotuning.
*2
NO
OK to operate
*3
YES
Stationary autotuning
*6
*6