Name
Con-
stant
Display
Number
Analog out-
Sets the signal output level for
put 1 signal
multi-function output 1 (terminal
level selec-
H4-07
FM)
tion
0: 0 to +10 V output
AO Level
1: 0 to ±10 V output
Select1
Channel 1
monitor
Effective when the Analog Monitor
selection
Card is used.
F4-01
Monitor selection:
AO Ch1
Set the number of the monitor item
Select
to be output. (U1-
Gain:
Channel 1
Set the multiple of 10 V for output-
gain
F4-02
ting monitor items.
AO Ch1 Gain
4, 10 to 14, 25, 28, 34, 39, 40 cannot
be set. 29 to 31 and 41 are not used.
Channel 2
When the AO-12 Analog Monitor
monitor
Card is used, outputs of ± 10 V are
selection
F4-03
possible. To output ± 10 V, set F4-
AO Ch2
07 or F4-08 to 1. When the AO-08
Select
Analog Monitor Card is used, only
outputs of 0 to +10 V are possible.
Channel 2
A meter calibration function is
gain
F4-04
available.
AO Ch2 Gain
Channel 1
Sets the channel 1 item bias to
output moni-
F4-05
100%/10 V when the analog moni-
tor bias
tor card is used.
AO Ch1 Bias
Channel 2
Sets the channel 2 item bias to
output moni-
F4-06
100%/10 V when the analog moni-
tor bias
tor card is used.
AO Ch2 Bias
Analog out-
put signal
level for
0: 0 to 10 V
F4-07
channel 1
1: -10 to +10 V
AO Opt
Level Sel
Analog out-
put signal
level for
0: 0 to 10 V
F4-08
channel 2
1: -10 to +10 V
AO Opt
Level Sel
Selecting Analog Monitor Items
The digital operator monitor items (U1-
terminals FM-AC and AM-AC. Refer to Chapter 5 User Constants, and set the values for the
(status monitor).
Alternatively, you can output monitor items (U1-
channels 1 and 2 on analog monitor cards AO-08 and AO-12. Refer to the table of constants, and set the val-
ues.
Setting
Description
Range
0 or 1
1 to 45
)
0.00 to
2.50
1 to 45
0.00 to
2.50
-10.0 to
10.0
-10.0 to
10.0
0 or 1
0 or 1
[status monitor]) are output from multi-function analog output
[status monitor]) from analog output option terminal
Control Methods
Change
Factory
during
V/f
Setting
Opera-
V/f
with
tion
PG
0
No
A
A
2
No
A
A
1.00
Yes
A
A
3
No
A
A
0.50
Yes
A
A
0.0
Yes
A
A
0.0
Yes
A
A
0
No
A
A
0
No
A
A
Monitor Constants
Open
Open
Flux
Loop
Loop
Vec-
Vector
Vector
tor
1
2
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
part of U1-
77
6-