Option Board Specifications - Omron MX2 DEVICENET OPTION BOARD User Manual

Mx2 devicenet option board
Table of Contents

Advertisement

Option Board Specifications

1-2
Option Board Specifications
Table 1 Option Board Specification
Item
Installation
Unit type
Model
Dimensions (W x H x D)
Weight
Environment
Ambient operating temperature
Ambient operating humidity
Ambient storage temperature
Vibration resistance
Dielectric strength
Conformance to EMC and Electri-
cal safety standards
Enclosure rating
DeviceNet
Communications protocol
Interface
Certification
DeviceNet Profile
Supported connections
Communications power supply
Unit device address range
Baud rates supported
DeviceNet
Default Connection path
Configuration
Supported Assemblies
EDS file
Note 1
Note 2
MX2 Series Option Board
3G3AX-MX2-DRT-E
68 x 58 x 45 mm
170g (typical)
-10 to 55°C (no icing or condensation)
20 to 90%RH
-20 to 65°C (no icing or condensation)
5.9m/s2 (0.6G) at 10...55Hz
500 VAC (between isolated circuits)
EN61800-3: 2004 (2004/108/EC) Second environment, Category
C3
EN61800-5-1: 2007 (2006/95/EC) SELV
IP 20
DeviceNet
DeviceNet Conformance Tested
AC Drive (0x02)
Remote I/O: Master-Slave connection
Poll
Bit-Strobe
COS
Cyclic
Explicit Messages
Conform to DeviceNet specifications
11 to 25 VDC
MAC ID 0 to 63, set with inverter parameter P192
125, 250 or 500 kbps. Automatically detecting baud rate of Master
Unit
Supported, set with inverter parameter P046
Basic Remote IO (Output assembly 20, Input assembly 70)
Extended Speed IO (21, 71)
Extended Speed and Torque Control (123, 173)
Special IO (100, 150)
Extended Control IO (101, 151)
Extended Control IO and Multi function IO monitor (101, 153)
Flexible Format (139, 159)
Extended Speed and Acceleration Control (110, 111)
In case the DeviceNet master is configured using user allocation,
only the input / output pairs can be configured.
Depending on the MX2-A@ inverter model (see below)
The derated- or ambient operating temperature of the MX2 Inverter takes pre-
cedence over that of the Option Board.
In case the 3G3AX-MX2-DRT-E is connected to the MX2-A@ Inverter, it is not
supported to connect any external devices to the RS485 (Modbus) interface
and the RJ45 port (Optional operator port) of the inverter.
Section 1-2
Specification